System Application Guide
SAG582136800
Spec. No. 582136800 (Model 502
NGFB
)
Revision BA, April 8, 2020
Page 29 of 129
List 91: Optional Temperature Probe, 33-Ft. Total Cable Length
Features
♦
See above for description of Temperature Probes.
♦
The Temperature Probe assembly consists of two pieces that plug together to make a complete probe. When ordered,
P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04116740 (30 feet long) is shipped loose. Total length: 33 ft.
Restrictions
See above for restrictions.
Ordering Notes
1)
Requires IB2 Interface Board (not included as standard in Lists 1, 3, 5, 6, 7 and 8).
2)
Order up to two (2) Temperature Probes for each system, as required. (Each List 91 includes one (1) P/N 04118246 and
one (1) P/N 04118247, and together makes up one temperature probe.)
3)
Only one (1) Temperature Probe can be used for compensation (in the SCU+). If multiple probes are required, order (1)
SM-TEMP Temperature Concentrator.
4)
See “Optional Temperature Probes” on page 68 for temperature probe options with a mounting tab.
List 93: Battery Tray Assembly, Pre-Cabled, for 23” Relay Rack
Features
♦
Provides one battery tray that mounts four (4) 12V front-terminal Valve Regulated
Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string.
♦
Accepts various VRLA batteries. See Ordering Notes below.
♦
See
Overall Dimensions – List 93 (23” Battery Tray)
PHYSICAL SIZE
INFORMATION
for battery tray dimensions and typical arrangement. Note that two
battery trays are available to accommodate the various size batteries listed in
Ordering Notes.
♦
Trays can be ordered with or without battery disconnect circuit breakers. When
circuit breakers are ordered, one is provided in the -48V lead of each battery string
(1 breaker per tray).
Restrictions
For 23” relay racks only.
A system e/w a one-row Distribution Cabinet can accommodate up to four (4) List 93’s,
depending on rack size and tray spacing.
A system e/w a two-row Distribution Cabinet can accommodate up to three (3) List 93’s,
depending on rack size and tray spacing.
When used with a List BA, BB or BC Distribution Cabinet equipped with 100A-200A
battery disconnect circuit breakers, a maximum of (3) battery trays can be used.
When used with a List BA, BB, BC, CA, CB or CC Distribution Cabinet equipped with 250A
battery disconnect circuit breakers, a maximum of (2) battery trays can be used.
Maximum gauge of factory-installed battery cabling is 1/0. If 250A battery disconnect is
used, this permits operation up through 40°C.
A single List 93 must mount at bottom of rack. Multiple List 93’s must mount starting at
bottom of rack and working upward.
561972 will fit into a 23" relay rack with upright depth of 5.00” (Telect Part
Number:12300KW201).
Ordering Notes
1)
Order multiples of List 93 for more than one (1) battery tray. See Restrictions above.
2)
Order one (1) or more P/N 362736700 Cable Bracket(s) as required.
3)
Order batteries separately. Tables A, B, C, and D list the batteries recommended for
use with List 93.
4)
Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery
clearance. See Tables A, B, C, and D.
P/N 561972