System Application Guide
SAG582136800
Spec. No. 582136800 (Model 502
NGFB
)
Revision BA, April 8, 2020
Page 69 of 129
Distribution Devices
Bullet Nose Type Circuit Breakers
Features
♦
Circuit breakers with ratings of 1A through 100A each plug into a single mounting position. Circuit breakers with ratings
of 125A, 150A and 200A each plug into two (2) mounting positions, and those with ratings of 250A each plug into three
(3) mounting positions.
Restrictions
Load should not exceed 80% of device rating.
Single Row Distribution Assembly: In a +40 °C ambient, 100 A circuit breakers can be used without a space provided the
continuous current in each device does not exceed 64 A. Overcurrent protective devices greater than 100 A shall have an
empty mounting position between it and any other overcurrent protective device.
At or above +65 °C, the maximum size overcurrent device used shall be 70 A. Devices rated at 70 A or less shall have an
empty mounting position between it and any other overcurrent protective device.
Two Row Distribution Assembly: In a +40 °C ambient, 100 A circuit breakers can be used without a space provided the
continuous current in each device does not exceed 64 A. 100 A fuses, 150 A and 250 A circuit breakers do not require a space
adjacent to it.
At or above +65°C, the maximum size circuit breaker used shall be 125 A. The maximum size fuse used shall be 70 A. Devices
rated at 50 A or greater shall have an empty mounting position between it and any other overcurrent protective device.
Ordering Notes
1)
Order circuit breakers, as required, per Table 7.
2)
For lug and wire size selection, refer to
BULLET NOSE-TYPE CIRCUIT BREAKERS
Ampere
Rating
Part Number
Electrical/
Mechanical Trip
1
(Black Handle)
Part Number
Electrical Trip
2
(White Handle)
Ampere
Rating
Part Number
Electrical/
Mechanical Trip
1
(Black Handle)
Part Number
Electrical Trip
2
(White Handle)
1
101596
102272
50
101606
102282
3
101597
102273
60
101607
102283
5
101598
102274
70
101608
102284
10
101599
102275
75
101609
102285
15
101600
102276
80
121995
121996
20
101601
102277
90
138888
138887
25
101602
102278
100
101610
102286
30
101603
102279
125
516838
516991
35
101604
102280
150
516839
516993
40
101605
102281
200
121832
121831
45
121997
121998
250
121836
121835
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
2
Provides an alarm during an electrical trip condition only.
Unless otherwise specified, breakers are to be mounted from right to left starting with the highest capacity and
working to the lowest capacity.
For 2-pole devices, either order lugs from
, or adapter kit 545404 and lugs from
For 3-pole devices, order adapter kit 545571 and lugs from
Table 7