background image

System Application Guide 

SAG582136800 

Spec. No. 582136800 (Model 502

NGFB

Revision BA, April 8, 2020 

 

 

 

 

 

 

Page 9 of 129 

  

 

MAIN COMPONENTS ILLUSTRATIONS 
Lists 1 - 4 

 

Home

 

NCU

 

IB2 Interface Board

 

(Available in List 1 and 

3) 

 

Rectifier  
Modules

 

Rectifier  
Modules

 

List 1

 

 

List 2

 

NCU

 

IB2 Interface Board

 

(Available in List 1 and 

3) 

 

Rectifier  
Modules

 

Rectifier  
Modules

 

List 3

 

 

 

List 4

 

Rear Plug-In AC Input Connectors. 

Rear DC Output Busbars. 

Summary of Contents for 582136800

Page 1: ... Output Termination Panel List No 19 or 23 Relay Rack Mounting Number of Power Shelves No of Rectifier Mounting Positions Output Capacity Amperes 5 19 1 Main 4 See Table 6 6 19 2 Main and Expansion 9 7 23 1 Main 5 8 23 2 Main and Expansion 11 Table 2 Assembled Shelves with Rear AC Input Configured for Top DC Distribution Cabinet List No 19 or 23 Relay Rack Mounting Number of Power Shelves No of Re...

Page 2: ...xpansion 14 27 23 3 1 Main 2 Expansion 17 Table 5 Output Capacities List No 208 240VAC Input 120VAC Input 40 C 65 C 40 C 65 C 1 166A 133A 105A 84A 2 208A 166A 131A 105A 3 208A 166A 131A 105A 4 250A 200A 157A 126A 5 166A 133A 105A 84A 6 374A 299A 236A 189A 7 208A 166A 131A 105A 8 400A 365A 290A 230A 10 166A 133A 105A 84A 11 374A 299A 236A 189A 12 208A 166A 131A 105A 13 458A 366A 288A 231A 14 208A 1...

Page 3: ... setting output voltage decreases as required to maintain output current at current limit Controller The controller controls the operation of the rectifier modules The controller also provides power system control metering monitoring and alarm functions NCU NetSure Control Unit The controller provides power system control including optional low voltage battery disconnect LVBD and low voltage load ...

Page 4: ... 11 and 13 7 4RU Lists List 21 and 23 8 75 5RU Lists List 6 8 16 and 17 10 5 6RU Lists List 26 and 27 12 25 7RU Note Heights refer to power shelves only Add the following for each selected Distribution Cabinet 1 row Distribution Cabinet 7 4RU 2 row Distribution Cabinet 14 8RU Note Heights refer to power shelves and space for List KG only Add the following for each selected Distribution Cabinet 1 r...

Page 5: ... Main Shelf Two 2 Expansion Shelves and Space for One 1 Distribution Cabinet 23 List 20 19 Assembled System with One 1 Main Shelf and Space for One 1 GMT Distribution Panel and One 1 Distribution Cabinet 23 List 21 19 Assembled System with One 1 Main Shelf One 1 Expansion Shelf and Space for One 1 GMT Distribution Panel and One 1 Distribution Cabinet 24 List 22 23 Assembled System with One 1 Main ...

Page 6: ...istribution Cabinet with 39 Load Positions 9 Battery Disconnect Positions and NO Low Voltage Disconnect LVD 55 List MD 23 2 Row Distribution Cabinet with 39 Load Positions 9 Battery Disconnect Positions Low Voltage Load Disconnect LVLD and Low Voltage Battery Disconnect LVBD 56 List MV 23 2 Row Distribution Cabinet with 48 Load Positions and NO Low Voltage Disconnect LVD 57 List NA 23 2 Row Distri...

Page 7: ...t Connections 89 Battery Connections 94 C O Ground Connection 95 External Alarm and Monitoring Connections 95 Wiring Illustrations 96 AC Input Connections All Lists 96 Bulk DC Output Connections Lists 1 4 98 Bulk DC Output and C O Ground Connections Lists 5 8 99 DC Load C O Ground and Battery Connections 1 Row Distribution Cabinets 100 List MA MD NA ND RA RD DC Load C O Ground and Battery Connecti...

Page 8: ...ensions List 20 with Distribution 120 Overall Dimensions List 21 with Distribution 121 Overall Dimensions List 22 with Distribution 122 Overall Dimensions List 23 with Distribution 123 Overall Dimensions List 26 with Distribution 124 Overall Dimensions List 27 with Distribution 125 Overall Dimensions List 93 23 Battery Tray 126 Overall Dimensions List 94 19 Battery Tray 127 BATTERY MANUFACTURER IN...

Page 9: ... 129 MAIN COMPONENTS ILLUSTRATIONS Lists 1 4 Home NCU IB2 Interface Board Available in List 1 and 3 Rectifier Modules Rectifier Modules List 1 List 2 NCU IB2 Interface Board Available in List 1 and 3 Rectifier Modules Rectifier Modules List 3 List 4 Rear Plug In AC Input Connectors Rear DC Output Busbars ...

Page 10: ...g In AC Input Connectors Top DC Output Busbars IB2 Interface Board Available in Lists 5 8 IB2 Interface Board Available in Lists 5 8 Rectifier Modules NCU Rectifier Modules IB2 Interface Board Available in Lists 5 8 NCU NCU Rectifier Modules IB2 Interface Board Available in Lists 5 8 List 5 List 6 List 7 List 8 Rectifier Modules NCU ...

Page 11: ...t IB2 Interface Board Included Distribution Cabinet Ordered under Lists FA GC 1 row shown or RA RD 2 row Rectifier Modules NCU IB2 Interface Board Included Rectifier Modules NCU IB2 Interface Board Included Distribution Cabinet Ordered under Lists AA CC 1 row shown or MA MD MV NA ND 2 row Rectifier Modules NCU IB2 Interface Board Included Rectifier Modules NCU List 10 List 11 List 12 List 13 ...

Page 12: ...es Rear Plug In AC Input Connectors Top DC Output Bus bars link to existing shelf Rectifier Modules List 14 List 15 List 16 List 17 IB2 Interface Board Included NCU Rectifier Modules IB2 Interface Board Included NCU Distribution Cabinet Ordered under Lists FA GC 1 row or RA RD 2 row shown Distribution Cabinet Ordered under Lists AA CC 1 row shown or MA MD MV NA ND 2 row Rear Plug In AC Input Conne...

Page 13: ...FA GC 1 row or RA RD 2 row shown Distribution Cabinet Ordered under Lists AA CC 1 row shown or MA MD MV NA ND 2 row Rectifier Modules IB2 Interface Board Included NCU IB2 Interface Board Included NCU IB2 Interface Board Included IB2 Interface Board Included NCU List 20 List 21 List 22 NCU List 23 GMT Distribution Panel Ordered under List KG Rectifier Modules Rectifier Modules Rectifier Modules GMT...

Page 14: ...tribution Cabinet List 26 List 27 IB2 Interface Board Included NCU IB2 Interface Board Included GMT Distribution Panel Ordered under List KG GMT Distribution Panel Ordered under List KG Distribution Cabinet Ordered under Lists FA GC 1 row or RA RD 2 row shown Distribution Cabinet Ordered under Lists AA CC 1 row shown or MA MD MV NA ND 2 row Rectifier Modules Rectifier Modules NCU ...

Page 15: ... No 582136800 Model 502NGFB Revision BA April 8 2020 Page 15 of 129 Other Other List Options List 89 Relay Rack Earthquake Anchor Kit List KG GMT Distribution Cabinet List 90 Temperature Probe List 93 Battery Tray 23 List 94 Batter Tray 19 Home ...

Page 16: ...CESSORY DESCRIPTIONS section 11 Order output lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section 12 Order one 1 standard mounting bracket kit P N 553336 or one 1 optional Knurr data cabinet flush mounting bracket kit P N 555231 as required See descriptions under the Accessory Descriptions section List 2 19 Expansion Shelf Features Consists of one 1 2RU high by 19 wide shelf Includes AC inpu...

Page 17: ...utput lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section List 4 23 Expansion Shelf Features Consists of one 1 2RU high by 23 wide shelf Includes AC input connectors and bulk output rear bus bars Houses up to six 6 Rectifier Modules Restrictions Requires one 1 List 3 A maximum of four 4 List 4 expansion shelves can be used with one 1 List 3 A List 4 MUST be mounted directly beneath List 3 o...

Page 18: ...o 2 2RU high by 19 wide rectifier shelves and one 1 2RU high by 19 termination panel pre assembled for 6RU total Termination panel includes AC input and DC output Bus bars System houses up to nine 9 Rectifier Modules and one 1 Controller A screw type terminal block is provided for connection of a battery and a load remote shunt Restrictions System is non expandable Ordering Notes 1 Order List 6 as...

Page 19: ...RY DESCRIPTIONS section List 8 23 Assembled System with One 1 Main Shelf One 1 Expansion Shelf and AC Input Bulk DC Output Termination Panel Features Consists of two 2 2RU high by 23 wide rectifier shelves and one 1 2RU high by 23 termination panel pre assembled for 6RU total Termination panel includes AC input and DC output Bus bars System houses up to eleven 11 Rectifier Modules and one 1 Contro...

Page 20: ...Order AC Input Cables and Line Cords per ACCESSORY DESCRIPTIONS section 11 Order Alarm Cables per ACCESSORY DESCRIPTIONS section 12 Order output lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section List 11 19 Assembled System with One 1 19 Main Shelf One 1 Expansion Shelf and Space for One 1 Distribution Cabinet Features Consists of two 2 2RU high by 19 wide rectifier shelves and interface f...

Page 21: ... to two 2 Temperature Probes List 90 or 91 as required See Optional Temperature Probes on page 68 for temperature probe options with a mounting tab 9 Order Relay Racks per ACCESSORY DESCRIPTIONS section 10 Order AC Input Cables and Line Cords per ACCESSORY DESCRIPTIONS section 11 Order Alarm Cables per ACCESSORY DESCRIPTIONS section 12 Order output lugs per Wiring Notes under ACCESSORY DESCRIPTION...

Page 22: ...anel P N PSK4830R 1 for each empty rectifier module mounting position in the system if required 4 Order AC Input Cables and Line Cords per ACCESSORY DESCRIPTIONS section List 15 23 Field Expansion Shelf Features Consists of a 2RU high by 23 wide shelf Includes AC input connectors and DC output bus bar links Accepts up to six 6 Rectifier Modules Restrictions For use with List 12 13 17 22 23 or 27 o...

Page 23: ...2RU high by 23 wide rectifier shelves and interface for pre assembled distribution Includes AC input connectors System accepts up to seventeen 17 Rectifier Modules one 1 Controller and one 1 Distribution Cabinet Includes IB2 Interface Board Restrictions The system is expandable by one 1 rectifier shelf in the field List 15 Ordering Notes 1 Order List 17 as required Also order the following as requ...

Page 24: ...tput lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section List 21 19 Assembled System with One 1 Main Shelf One 1 Expansion Shelf and Space for One 1 GMT Distribution Panel and One 1 Distribution Cabinet Features Consists of two 2 2RU high by 19 wide rectifier shelves and interface for pre assembled distribution Includes AC input connectors System houses up to nine 9 Rectifier Modules one 1 ...

Page 25: ...hor Kit s List 89 as required 9 Order up to two 2 Temperature Probes List 90 or 91 as required See Optional Temperature Probes on page 68 for temperature probe options with a mounting tab 10 Order Relay Racks per ACCESSORY DESCRIPTIONS section 11 Order AC Input Cables and Line Cords per ACCESSORY DESCRIPTIONS section 12 Order Alarm Cables per ACCESSORY DESCRIPTIONS section 13 Order output lugs per...

Page 26: ... Rectifier Modules P N 1R482000e per system 3 Order one 1 optional Rectifier Module Mounting Position Blank Cover Panel P N PSK4830R 1 for each empty rectifier module mounting position in the system if required 4 Order one 1 NCU P N 1M830BNA Controller per system Also specify appropriate configuration file for your site 5 Order one 1 Distribution Cabinet List FA FB FC GA GB GC RA RB RC or RD per s...

Page 27: ...ate configuration file for your site 5 Order one 1 Distribution Cabinet List AA AB AC BA BB BC CA CB CC MA MB MC MD MV NA NB NC or ND per system 6 Order one 1 GMT Panel List KG per system 7 Order Battery Trays List 93 as required 8 Order Relay Rack Anchor Kit s List 89 as required 9 Order up to two 2 Temperature Probes List 90 or 91 as required See Optional Temperature Probes on page 68 for temper...

Page 28: ... to temperature is maintained If the system is equipped with the ACU or NCU Controller a temperature probe set as a battery probe can also be used for controlling against battery thermal runaway BTRM feature The Temperature Probe assembly consists of two pieces that plug together to make a complete probe When ordered P N 04118246 3 feet long is pre wired to the shelf P N 04118247 9 feet long is sh...

Page 29: ...ays are available to accommodate the various size batteries listed in Ordering Notes Trays can be ordered with or without battery disconnect circuit breakers When circuit breakers are ordered one is provided in the 48V lead of each battery string 1 breaker per tray Restrictions For 23 relay racks only A system e w a one row Distribution Cabinet can accommodate up to four 4 List 93 s depending on r...

Page 30: ...er per List 93 from Table F 8 If ordering List 93 with tray mounted circuit breakers specify breaker mounting on left or right side of tray Circuit breaker mounting kits shown in the Table F will be installed Kit numbers are provided for reference only 9 If ordering List 93 with tray mounted circuit breakers order Alarm Jumper P N 524384 for each system to connect the alarm terminal of up to three...

Page 31: ...ing information Table B Battery Tray P N 559808 Manufacturer Model Vertiv P N Rated 8 Hr Capacity Ah Dimension W x L x H Inches Required Tray Spacing Weight per battery lbs Enersys 12TD150F 143 4 3 X 21 7 X 11 3 8U 105 See Battery Manufacturer Information located at the end of this document Table C Battery Tray P N 561972 Manufacturer Model Vertiv P N Rated 8 Hr Capacity Ah Dimension W x L x H Inc...

Page 32: ...1 0 AWG Douglas DGS12 150F Douglas DSN12 170F 528234 2 AWG 528235 1 0 AWG Northstar NSB40FT Northstar NSB60FT Douglas DGS12 25F Douglas DGS12 50F Enersys 12TD50F Enersys 12TD150F Table E Ampere Rating Part No Circuit Breaker Electrical Mechanical Trip1 Black Handle Part No Left Side Breaker Mtg Kit For Reference Only Part No Right Side Breaker Mtg Kit For Reference Only 50 256694300 559814 559813 ...

Page 33: ...tiple List 94 s must mount starting at bottom of rack and working upward 561974 will fit into a 19 relay rack with upright depth of 5 00 Telect Part Number 12545 300 Ordering Notes 1 Order multiples of List 94 for more than one 1 battery tray See Restrictions above 2 Order one 1 or more P N 362736700 Cable Bracket s as required 3 Order batteries separately Tables G H I J and K list batteries recom...

Page 34: ...n W x L x H Inches Required Tray Spacing Weight per Battery lbs Enersys 12TD100F6 97 4 3 X 20 0 X 9 4 7U 73 See Battery Manufacturer Information located at the end of this document Table H Battery Tray P N 559811 Manufacturer Model Vertiv P N Rated 8 Hr Capacity Ah Dimension W x L x H Inches Required Tray Spacing Weight per Battery lbs Northstar NSB40FT 38 1 3 80 X 9 80 X 8 20 6U 34 Northstar NSB6...

Page 35: ...on W x L x H Inches Required Tray Spacing Weight per battery lbs Enersys 12V125F 122009 125 4 10 X 22 10 X 12 40 8U 124 Enersys 12TD150F 143 4 3 X 21 7 X 11 3 8U 105 See Battery Manufacturer Information located at the end of this document Table K Battery Specified Battery Lug Kit Part Number Kit provides two lugs for one tray Up to 150A Battery Disconnect Above 150A or No Battery Disconnect chosen...

Page 36: ...l Mechanical Trip1 Black Handle Part No Left Side Breaker Mtg Kit For Reference Only Part No Right Side Breaker Mtg Kit For Reference Only 50 256694300 559814 559813 60 256694700 70 256695100 75 256695500 100 256695900 125 100765 559816 559815 150 100763 200 121810 559816 559815 1 Provides an alarm during an electrical or manual trip condition Table M Home ...

Page 37: ...en it and any other overcurrent protective device Includes 1 Low Voltage Battery Disconnect Contactor LVBD Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribu...

Page 38: ...ny other overcurrent protective device Includes 1 Low Voltage Load Disconnect Contactor LVLD Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet t...

Page 39: ... position between it and any other overcurrent protective device Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution a...

Page 40: ...t and any other overcurrent protective device Includes 1 Low Voltage Battery Disconnect Contactor LVBD Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution...

Page 41: ...t and any other overcurrent protective device Includes 1 Low Voltage Load Disconnect Contactor LVLD Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Ca...

Page 42: ...ounting position between it and any other overcurrent protective device Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distrib...

Page 43: ...t and any other overcurrent protective device Includes 1 Low Voltage Battery Disconnect Contactor LVBD Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution...

Page 44: ...t and any other overcurrent protective device Includes 1 Low Voltage Load Disconnect Contactor LVLD Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Ca...

Page 45: ...nting position between it and any other overcurrent protective device Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribut...

Page 46: ...ny other overcurrent protective device Includes 1 Low Voltage Battery Disconnect Contactor LVBD Restrictions This Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabine...

Page 47: ...ny other overcurrent protective device Includes 1 Low Voltage Load Disconnect Contactor LVLD Restrictions This Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet t...

Page 48: ...ny other overcurrent protective device Restrictions This Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling Unless ...

Page 49: ...t and any other overcurrent protective device Includes 1 Low Voltage Battery Disconnect Contactor LVBD Restrictions This Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution...

Page 50: ...t and any other overcurrent protective device Includes 1 Low Voltage Load Disconnect Contactor LVLD Restrictions This Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Ca...

Page 51: ...ounting position between it and any other overcurrent protective device Restrictions This Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distrib...

Page 52: ... 40 C and 80A 65 C Can be mounted in 19 or 23 racks Factory mounted and connected when ordered with power system If the Distribution Cabinet in the system is equipped with Low Voltage Load Disconnect LVLD all List KG loads are unaffected by the LVLD If one or more distribution fuses opens one set of Form C relay contacts changes state and resistive battery is provided to an alarm terminal Alarm ci...

Page 53: ...nect Contactor LVBD Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling Unless otherwise specified...

Page 54: ...t disconnects 24 positions in Top Row Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling Unless o...

Page 55: ...s Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling Unless otherwise specified fuses and or circuit breakers are m...

Page 56: ... the 24 load positions in the top row It also contains a low voltage battery disconnect Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to acc...

Page 57: ...vercurrent protective device Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling Unless otherwise ...

Page 58: ...device Includes 1 Low Voltage Battery Disconnect Contactor LVBD Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution an...

Page 59: ... Low Voltage Load Disconnect Contactor LVLD that disconnects 24 positions in Top Row Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accomm...

Page 60: ...ercurrent protective device Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling Unless otherwise s...

Page 61: ...low voltage load disconnect that disconnects the 24 load positions in the top row It also contains a low voltage battery disconnect Restrictions This Distribution Cabinet can be used in List 12 13 17 22 23 or 27 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be pro...

Page 62: ...connect Contactor LVBD Restrictions This Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling Unless otherwise specif...

Page 63: ...nnects the 19 load positions in the Top Row Restrictions This Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling Un...

Page 64: ...s Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling Unless otherwise specified fuses and or circuit breakers are m...

Page 65: ...s a low voltage battery disconnect Includes 1 Low Voltage Battery Disconnect contactor LVBD and 1 Low Voltage Load Disconnect contactor LVLD Restrictions This Distribution Cabinet can be used in List 10 11 16 20 21 or 26 only The system is designed for a maximum of one 1 Distribution Cabinet The Distribution Cabinet is assembled immediately above the power shelf Adequate vertical mounting space mu...

Page 66: ... NCU controller This is identified by a six digit number If the controller part number ends with a six digit number for example 1M830BNA559242 the configuration file number is the last six characters If the part number does not have these characters the configuration file number can be found on the controller nameplate Programmed with Configuration File The user manual provided with the controller...

Page 67: ...alarm relays and connections for seven 7 digital control inputs Connects to the controller via cables Restrictions For use in Lists 1 3 5 6 7 8 10 11 12 13 16 17 20 21 22 23 26 and 27 only Always included in Lists 10 11 12 13 16 17 20 21 22 23 26 and 27 Required for Lists 1 3 5 6 7 and 8 when used with NCU P N 1M830BNA Ordering Notes Order one 1 IB2 Interface Board Assembly P N 548181 for each Lis...

Page 68: ...aintained If the system is equipped with the ACU or NCU Controller a temperature probe set as a battery probe can also be used for controlling against battery thermal runaway BTRM feature The temperature sensor end of the probe contains a tab with a 5 16 clearance hole for mounting The Temperature Probe assembly consists of two pieces that plug together to make a complete probe Restrictions A temp...

Page 69: ...above 65 C the maximum size circuit breaker used shall be 125 A The maximum size fuse used shall be 70 A Devices rated at 50 A or greater shall have an empty mounting position between it and any other overcurrent protective device Ordering Notes 1 Order circuit breakers as required per Table 7 2 For lug and wire size selection refer to Table 15 BULLET NOSE TYPE CIRCUIT BREAKERS Ampere Rating Part ...

Page 70: ...e 1 Part No 117201 TPS TLS type fuse holder for each fuse 3 For lug and wire size selection refer to refer to Table 15 TPS TLS TYPE FUSES Ampere Rating Part Number Ampere Rating Part Number 3 248230900 40 248233300 5 248231000 50 248233900 6 248231200 60 248234200 10 248231500 70 248234500 15 248231800 80 118413 20 248232100 90 118414 25 248232400 100 118415 30 248232700 TPS TLS Type Fuseholder 11...

Page 71: ...g Notes 1 Order GMT fuses per Table 9 GMT FUSES Ampere Rating Part Number Fuse Color Ampere Rating Part Number Fuse Color 18 100 GMT A 248610301 5 248611000 Green 1 4 248610200 Violet 7 1 2 248611300 Black White 1 2 248610300 Red 10 248611200 Red White 3 4 248610500 Brown 15 248611500 Red Blue 1 1 3 248610700 White Replacement Dummy Fuse 248872600 2 248610800 Orange Replacement Safety Fuse Cover 1...

Page 72: ...se specified Maximum size of wire to be connected to a single fuse position is 14 AWG Cannot be installed in positions 3 4 5 12 or 13 of all 23 1 row cabinets Lists AA AB AC BA BB BC CA CB CC Cannot be installed in positions 3 4 5 9 or 10 of all 19 1 row cabinets lists FA FB FC GA GB GC Ordering Notes 1 Order P N 545333 for 1 row Distribution Cabinets and P N 549017 for 2 Row Distribution Cabinets...

Page 73: ...ar Adapter Kit Converts 2 load positions 1 4 20 on 5 8 centers to 1 landing 3 8 16 on 1 centers Right angle Load busbar straight Return busbar for rear wiring egress 545405 Busbar Adapter Kit Converts 1 load position 1 4 20 on 5 8 centers to 1 load landing 1 4 20 on 5 8 centers right angle 545571 Busbar Adapter Kit Converts 3 load positions 1 4 20 on 5 8 centers to 1 landing 3 8 16 on 1 centers Ri...

Page 74: ...5 studs provided P N 557233 is for 19 2 Row distribution cabinets and has 19 return landing positions 1 4 20 x 0 75 studs provided Restrictions P N 556891 is for use with lists MA MB MC MD NA NB NC and ND only P N 557233 is for use with lists RA RB RC and RD only Ordering Notes 1 Order P N 556891 or P N 557233 for 2 row distribution cabinets as required Note Existing front facing bars will need to...

Page 75: ...des 8 temperature probe inputs per SM TEMP Can be cascaded up to 8 SM TEMP modules connecting up to sixty four 64 temperature probes Provides analog output for all controllers Provides CAN output for ACU and NCU In the ACU and NCU the SM Temp Concentrator can be connected at the end of the ACU or NCU CAN bus Via the CAN Bus the ACU and NCU reads each temperature probe from each SM Temp Concentrato...

Page 76: ... of two brackets and hardware for mounting a List 1 or List 2 power shelf into a 19 wide relay rack P N 555231 consists of two brackets and hardware for flush mounting a List 1 or List 2 into a 19 4 493mm wide rack of a Knurr data cabinet Restrictions For use with List 1 and List 2 only Ordering Notes 1 Order mounting kit P N 553336 or P N 555231 as required P N 555231 P N 553336 Home ...

Page 77: ...re for mounting a List 10 power shelf and a List FA FB FC GA GB or GC distribution shelf into a 19 wide rack of a Knurr data cabinet one set of brackets mounts both shelves Restrictions P N 556342 is for use with List FA FB FC GA GB or GC only P N 556343 is for use with List 10 only P N 556346 is for use with a List 10 and List FA FB FC GA GB or GC together only only one set of mounting brackets r...

Page 78: ...SAG582136800 System Application Guide Revision BA April 8 2020 Spec No 582136800 Model 502NGFB Page 78 of 129 P N 556342 P N 556346 P N 556343 Home ...

Page 79: ... for securing the wall mount bracket to the wall System mounting angles cannot be in the flush front mount position Ordering Notes 1 Order by P N 552537 as required Optional 23 6RU Wall Mount Bracket Kit P N 552535 Features Allows for horizontal wall mounting of 23 systems See Overall Dimensions System with 23 6RU Wall Mount Kit P N 552535 cont d on next page on page 114 for mounting dimensions Re...

Page 80: ...Two hole lug 3 8 clearance holes on 1 centers for power shelf connection Two hole lug 1 4 clearance holes on 5 8 centers for termination panel connection For use with 582136800 List 1 P N 555233 One 1 24 long 4 0 AWG cable provided for each polarity Two hole lug 3 8 clearance holes on 1 centers for power shelf connection Two hole lug 1 4 clearance holes on 5 8 centers for termination panel connect...

Page 81: ... One 1 24 long 4 0 AWG cable provided for each polarity Two hole lug 3 8 clearance holes on 1 centers for power shelf connection Two hole 90 degree lug 1 4 clearance holes on 5 8 centers for termination panel connection For use with 582136800 List 2 P N 556440 One 1 24 long 2 0 AWG cable provided for each polarity Two hole lug 3 8 clearance holes on 1 centers for power shelf connection Two hole 90...

Page 82: ...84 00 H x 23 W 45RU Welded 562353 See Note 7 0 H x 23 W 6 W Mounting Rails 45RU Seismic complies with Bellcore Seismic Zone 4 requirements 562355 85 75 H x 23 W 46RU Seismic complies with Bellcore Seismic Zone 4 requirements 559821 90 00 H x 23 W 48RU Welded 559822 8 0 H x 23 W 51RU Welded 19 Relay Racks 559823 7 0 H x 19 W 45RU Seismic complies with Bellcore Seismic Zone 4 requirements 559824 7 0...

Page 83: ...e patterns and hardware 3 8 to mount the plates to the above listed relay racks Customer must supply hardware to mount the transition plates to the battery stands Restrictions Used with relay rack P N 543156 only Ordering Notes 1 Order P N 509819 for a Transition Plate Kit to mount relay rack on top of battery with outside dimensions of 26 75 x 26 38 35 75 x 26 38 or 42 50 x 26 38 2 Order P N 5148...

Page 84: ... Assemblies or Line Cords Lists 16 and 26 require eight 8 AC Input Cable Assemblies or Line Cords Lists 17 and 27 require nine 9 AC Input Cable Assemblies or Line Cords AC Input Cable Assembly P N 553202 Features Provides one 1 12 long 8 AWG AC Input Cable Assembly that is Terminated on one end with a Molex plug which mates with AC input receptacle on the Power Shelf and Not terminated on the rema...

Page 85: ...ts 16 and 26 require eight 8 AC Input Cable Assemblies or Line Cords Lists 17 and 27 require nine 9 AC Input Cable Assemblies or Line Cords AC Input Line Cord P N 559301 Features Provides one 1 14 long 8 3 AWG AC Input Line Cord that is terminated on one end with a Molex plug at a 90 degree angle bend which mates with AC input receptacle on the Power Distribution Shelf and on the remaining end wit...

Page 86: ... is terminated on one end with a Molex plug at a 90 degree angle bend which mates with AC input receptacle on the Power Distribution Shelf and on the remaining end with a NEMA L6 30P twist lock plug Restrictions For 208 240 VAC only rated for 30A at 208 240VAC Ordering Notes 1 Order AC Input Cable Assemblies or Line Cords as required Lists 1 5 10 and 20 require two 2 AC Input Cable Assemblies or L...

Page 87: ... If a relay rack and power system are ordered along with the brackets the brackets will be mounted to the rack at the factory Battery Cables P N 559124 Features Provides two 2 3 long 2 AWG battery cables terminated in a 2 position Red SB120 Anderson connector Remaining end terminated in lugs for connection to the distribution unit Restrictions For use with Lists AA AB AC FA FB and FC only Ordering...

Page 88: ...vanced Controller Unit Plus Order per P N 1M830BNA IB2 Interface Board Order per P N MA4C5U31 Temperature Probe 3 Meter Order per List 90 or if only one piece of the two piece probe is needed see the list 90 description for part numbers See Optional Temperature Probes on page 68 for temperature probe options with a mounting tab Temperature Probe 10 Meter Order per List 91 See Optional Temperature ...

Page 89: ... lugs Lists 5 8 3 8 16 studs on 1 centers are provided for installation of customer furnished DC output cables terminated in two hole lugs Lists 10 13 and 16 27 Distribution Cabinets provide 1 4 20 studs on 5 8 centers for installation of customer furnished DC Load and Load Return distribution cables terminated in two hole lugs Lists 14 15 These field expansion shelves are furnished with output bu...

Page 90: ...4 2 1 0 AWG 2 245347100 65 133 89 2 2 AWG 2 245348200 143 2 1 0 AWG 2 245347100 Table 14A Recommended DC Output Wire Size PER SHELF and Lug Selection LISTS 1 and 5 Input Voltage VAC Ambient Operating Temp 1 Max Total Output Curr Amps Loop Length Ft 1 0 Volt Drop 2 Recm 90 C Wire Size Recm Crimp Lug 3 120 40 131 36 2 6 AWG 2 245349900 72 1 1 0 AWG 1 245347100 91 1 2 0 AWG 1 245347200 65 105 114 1 2...

Page 91: ...2 0 AWG 2 245347200 151 2 3 0 AWG 2 245347300 Table 14C Recommended DC Output Wire Size PER SHELF and Lug Selection LIST 4 Input Voltage VAC Ambient Operating Temp 1 Max Total Output Curr Amps Loop Length Ft 1 0 Volt Drop 2 Recm 90 C Wire Size Recm Crimp Lug 3 120 40 236 50 2 2 AWG 2 245348200 76 3 2 AWG 3 245348200 80 2 1 0 AWG 2 245347100 65 189 94 3 2 AWG 3 245348200 100 2 1 0 AWG 2 245347100 1...

Page 92: ...and Lug Selection LIST 8 Notes to Tables 14A 14E 1 Wire sizes are based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 16 for copper wire rated at 90 C conductor temperature operating in ambient temperatures of 40 C and 65 C was used For other operating ambient temperatures refer to th...

Page 93: ...3 4 5 149 3 4 5 45A 33 3 4 52 3 4 83 3 4 132 3 4 50A 29 3 47 3 4 75 3 4 119 3 4 60A 39 3 4 62 3 4 99 3 4 70A 53 3 4 85 3 4 75A 50 3 4 79 3 4 80A 47 3 74 3 4 Recommended Crimp Lug 6 Lug 245342300 245342300 245342300 245390200 245346700 245346800 245346900 Fuse Circuit Breaker Amperage Recm 90 C Wire Size 1 2 AWG 1 0 AWG 2 0 AWG 3 0 AWG 4 0 AWG 250 kcmil 350 kcmil Loop Length feet 2 90A 66 3 4 105 3...

Page 94: ...ose Type Circuit Breaker Load and Load Return Battery Connections Features In each Distribution Cabinet lug terminated battery conductors are connected to the battery terminals as follows Each Distribution Cabinet provides the following connection points for two hole lug terminated battery wires Lists AA AB AC FA FB FC and MV Battery and Battery Return busbars provide 3 8 threaded studs on 1 cente...

Page 95: ...ional Standards Institute ANSI approved National Fire Protection Association s NPFA National Electrical Code NEC applicable local codes and your specific site requirements All lugs for customer connections must be ordered separately Customer to supply lug mounting hardware External Alarm and Monitoring Connections Features Alarm output and monitoring input leads are connected to screw type termina...

Page 96: ...SAG582136800 System Application Guide Revision BA April 8 2020 Spec No 582136800 Model 502NGFB Page 96 of 129 Wiring Illustrations AC Input Connections All Lists Home ...

Page 97: ...System Application Guide SAG582136800 Spec No 582136800 Model 502NGFB Revision BA April 8 2020 Page 97 of 129 Home ...

Page 98: ...Page 98 of 129 Bulk DC Output Connections Lists 1 4 DC Output Busbars Clearance Holes for 3 8 Bolts for Installation of Customer Furnished Two hole Lugs Slip bus bar through slot before connecting lug to busba r Fold around lug after securing lug to busbar 1 1 DC Output List 1 4 List 1 Shown Home ...

Page 99: ...DC Output List 5 8 List 7 Shown 48V Return RTN 48V 1 00 1 15 C O Ground 48V RETURN DC Output List 5 and 6 Top View 3 8 16 threaded studs for installation of customer furnished two hole lugs DC Output List 7 and 8 Top View 3 8 16 threaded studs for installation of customer furnished two hole lugs 48V RTN 48V Cabinet Rear RETURN RTN 1 00 1 15 C O Ground Home Home ...

Page 100: ...tuds on 5 8 centers Lug Spacing 0 765 center to center 48V Load 48V Battery See specific configurations below 1 4 20 studs on 5 8 centers Lug Spacing 0 765 center to center Lists AA AB AC 48V Load Distribution Positions 24 Lists BA BB BC 48V Load Distribution Positions 18 48V Battery Disconnect Positions 6 Lists CA CB CC 48V Load Distribution Positions 16 48V Battery Disconnect Positions 8 Lists F...

Page 101: ...8 centers Lug Spacing 0 765 center to center 48V Load All 2 Row Lists 1 4 20 studs on 5 8 centers Lug Spacing 0 765 center to center Lists MA MB MC MD 48V Load Distribution Positions 15 48V Battery Disconnect Positions 9 48V Load Distribution Positions 24 Lists NA NB NC ND 48V Load Distribution Positions 4 48V Battery Disconnect Positions 20 48V Load Distribution Positions 24 C O Ground All 2 Row ...

Page 102: ... omitted Load Return Busbars Qty 48 Lug Positions 1 4 20 studs on 5 8 centers Lug Spacing 0 765 center to center 48V Load Qty 48 Breaker and Lug Positions 1 4 20 studs on 5 8 centers Lug Spacing 0 765 center to center Front Battery Return and C O Ground Qty 3 Lug Positions 3 8 16 studs on 1 centers Lug Spacing 1 center to center 48V Battery Qty 2 Lug Positions 3 8 16 studs on 1 centers Lug Spacing...

Page 103: ...itoring Wiring Note A custom digital input cable and internal wiring kit is available P N 559963 This kit is factory installed only Provides 48 VDC pre wired to the negative side of digital inputs 4 through 7 and a 10 alarm cable factory wired to the positive side of digital inputs 4 through 7 Home Home Home Home Home Home Home Home ...

Page 104: ... 120VAC List 5 105 1 4 AWG 12 3 84 1 2 AWG 24 4 List 6 236 6 1 0 AWG 13 8 189 3 3 0 AWG 27 4 List 7 131 4 2 AWG 15 5 105 2 2 AWG 19 5 List 8 289 2 4 0 AWG 22 7 231 4 4 0 AWG 28 3 Notes 1 The shunt connected to these terminals must be connected to the output cables of this plant within these maximum distances for the cable sizes used Loop length is the sum of the lengths of the positive and negativ...

Page 105: ...he relay rack and 2 for the rear of the relay rack Separate shelves are available for mounting in either a 19 or 23 wide relay rack 1 or 1 3 4 multiple drilling Mounting angles are positioned for a 5 inch front projection mounting only 1 1 6 Ventilation Requirements Rectifier and mounting shelf ventilating openings must not be blocked and temperature of air entering rectifiers must not exceed rate...

Page 106: ...NS 1 3 3 Alarm and Monitoring Connections Alarm output and monitoring input leads are connected to screw type terminal blocks located on the IB2 Interface Board located inside the shelf These leads enter the right side as viewed from the front of the shelf and are accessible from the front of the shelf Alarm cables are available 1 3 4 Dimensions and Weights Refer to the illustrations under Physica...

Page 107: ...t 2 Rectifiers Ordered Separately Top View Left Side View Right Side View Bottom View Rear View Front View 17 25 13 75 Notes 1 All dimensions are in inches unless otherwise specified 2 Finish Galvanized steel with light gray paint on front face 3 Weight without rectifiers List 1 12 21 lbs List 2 10 21 lbs 3 50 12 50 5 00 2 00 3 00 18 31 19 00 0 250 x 0 375 Slot Home ...

Page 108: ...s Ordered Separately Top View Left Side View Right Side View Bottom View Rear View Front View 20 65 13 75 Notes 1 All dimensions are in inches unless otherwise specified 2 Finish Galvanized steel with light gray paint on front face 3 Weight without rectifiers List 3 14 25 lbs List 4 12 25 lbs 3 50 2 00 23 00 22 31 5 00 12 50 3 00 0 250 x 0 375 Slot Home ...

Page 109: ...tes 1 All dimensions are in inches unless otherwise specified 2 Finish Galvanized steel with light gray paint on front face 3 Weight without rectifiers 27 00 lbs Mounting Hole Detail 0 250 0 500 Dia 0 880 See Mounting Hole Detail See Mounting Hole Detail Top View Left Side View Right Side View Bottom View Rear View Front View 10 50 17 25 18 31 19 00 Notes 1 All dimensions are in inches unless othe...

Page 110: ...ized steel with light gray paint on front face 3 Weight without rectifiers 30 00 lbs 6 73 1 48 5 48 3 23 List 7 List 8 Mounting Hole Detail 0 250 0 500 Dia 0 880 Mounting Hole Detail 0 250 0 500 Dia 0 880 Top View Left Side View Bottom View Rear View Front View 10 50 20 65 22 31 23 00 Notes 1 All dimensions are in inches unless otherwise specified 2 Finish Galvanized steel with light gray paint on...

Page 111: ...bution Cabinet 21 21 lbs For 1 Row Dist Cabinet add 32 75 lbs For 2 Row Dist Cabinet add 65 5 lbs 4 Overall Mounting Height 10 50 with 1 Row Dist Cabinet shown 17 50 with 2 Row Dist Cabinet Top View Left Side View Front View 13 73 10 73 10 23 7 23 3 73 3 23 6 73 Rear View 19 44 18 31 17 25 Right Side View 5 00 12 62 13 19 See Note 4 0 23 0 250 Dia 0 250 Dia Notes 1 All dimensions are in inches unl...

Page 112: ...G582136800 System Application Guide Revision BA April 8 2020 Spec No 582136800 Model 502NGFB Page 112 of 129 Home Overall Dimensions System with 19 6RU Wall Mount Kit P N 552537 cont d on next page 552537 ...

Page 113: ...FB Revision BA April 8 2020 Page 113 of 129 Home Overall Dimensions System with 19 6RU Wall Mount Kit P N 552537 cont d from previous page Notes 1 All dimensions are in inches unless otherwise specified Top View Right Side View Front View Left Side View 17 6 10 5 19 2 ...

Page 114: ...G582136800 System Application Guide Revision BA April 8 2020 Spec No 582136800 Model 502NGFB Page 114 of 129 Home Overall Dimensions System with 23 6RU Wall Mount Kit P N 552535 cont d on next page 552535 ...

Page 115: ...FB Revision BA April 8 2020 Page 115 of 129 Home Overall Dimensions System with 23 6RU Wall Mount Kit P N 552535 cont d from previous page Notes 1 All dimensions are in inches unless otherwise specified Top View Right Side View Front View Left Side View 10 5 23 4 17 7 ...

Page 116: ...Cabinet 26 50 lbs For 1 Row Dist Cabinet add 37 75 lbs For 2 Row Dist Cabinet add 74 25 lbs 4 Overall Mounting Height 14 00 with 1 Row Dist Cabinet shown 21 00 with 2 Row Dist Cabinet Top View Left Side View Bottom View Rear View Front View 23 44 13 73 10 73 10 23 7 23 6 73 3 73 22 31 21 34 Right Side View 5 00 12 62 13 19 3 23 See Note 4 0 23 0 250 Dia Notes 1 All dimensions are in inches unless ...

Page 117: ...2 Finish Galvanized steel with light gray paint on front face 3 Weight without rectifiers 10 21 lbs 17 25 18 31 19 00 2 00 3 00 5 00 12 50 13 19 3 50 Rear View List 14 0 250 x 0 375 Slot 0 250 x 0 375 Slot Top View Left Side View Bottom View Rear View Front View Notes 1 All dimensions are in inches unless otherwise specified 2 Finish Galvanized steel with light gray paint on front face 3 Weight wi...

Page 118: ...inish Galvanized steel with light gray paint on front face 3 Net Weight without rectifiers and Distribution Cabinet 32 63 lbs For 1 Row Dist Cabinet add 32 75 lbs For 2 Row Dist Cabinet add 65 5 lbs 4 Overall Mounting Height 17 50 with 1 Row Dist Cabinet 24 50 with 2 Row Dist Cabinet shown Top View Left Side View Bottom View Front View Right Side View 5 00 12 62 13 19 17 50 17 23 14 23 6 73 3 73 3...

Page 119: ...2 Finish Galvanized steel with light gray paint on front face 3 Net Weight without rectifiers and Distribution Cabinet 38 75 lbs For 1 Row Dist Cabinet add 37 75 lbs For 2 Row Dist Cabinet add 74 25 lbs 4 Overall Mounting Height 17 50 with 1 Row Dist Cabinet shown 24 50 with 2 Row Dist Cabinet Top View Left Side View Bottom View Front View Right Side View 5 00 12 62 13 19 17 23 14 23 6 73 3 73 3 2...

Page 120: ...h Galvanized steel with light gray paint on front face 3 Net Weight without rectifiers List KG and Distribution Cabinet 12 21 lbs For 1 Row Dist Cabinet add 32 75 lbs For 2 Row Dist Cabinet add 65 5 lbs For List KG add 9 lbs 4 Overall Mounting Height 12 25 with 1 Row Dist Cabinet 19 25 with 2 Row Dist Cabinet shown Top View Left Side View Bottom View Front View Right Side View 5 00 12 62 13 19 12 ...

Page 121: ...alvanized steel with light gray paint on front face 3 Net Weight without rectifiers List KG and Distribution Cabinet 22 42 lbs For 1 Row Dist Cabinet add 32 75 lbs For 2 Row Dist Cabinet add 65 5 lbs For List KG add 9 lbs 4 Overall Mounting Height 15 75 with 1 Row Dist Cabinet 22 75 with 2 Row Dist Cabinet shown Top View Left Side View Bottom View Front View Right Side View 5 00 12 62 13 19 15 48 ...

Page 122: ...ish Galvanized steel with light gray paint on front face 3 Net Weight without rectifiers List KG and Distribution Cabinet 14 25 lbs For 1 Row Dist Cabinet add 37 75 lbs For 2 Row Dist Cabinet add 74 25 lbs For List KG add 9 lbs 4 Overall Mounting Height 12 25 with 1 Row Dist Cabinet shown 19 25 with 2 Row Dist Cabinet Top View Left Side View Bottom View Front View Right Side View 5 00 12 62 13 19 ...

Page 123: ... Galvanized steel with light gray paint on front face 3 Net Weight without rectifiers List KG and Distribution Cabinet 26 50 lbs For 1 Row Dist Cabinet add 37 75 lbs For 2 Row Dist Cabinet add 74 25 lbs For List KG add 9 lbs 4 Overall Mounting Height 15 75 with 1 Row Dist Cabinet shown 22 75 with 2 Row Dist Cabinet Top View Left Side View Bottom View Front View Right Side View 5 00 12 62 13 19 Rea...

Page 124: ...ed steel with light gray paint on front face 3 Net Weight without rectifiers List KG and Distribution Cabinet 32 63 lbs For 1 Row Dist Cabinet add 32 75 lbs For 2 Row Dist Cabinet add 65 5 lbs For List KG add 9 lbs 4 Overall Mounting Height 19 25 with 1 Row Dist Cabinet 26 25 with 2 Row Dist Cabinet shown Top View Left Side View Bottom View Front View Right Side View 5 00 12 62 13 19 12 48 6 73 3 ...

Page 125: ...9 12 48 6 73 3 73 3 23 10 73 10 23 7 23 Rear View 23 44 22 31 21 34 15 98 18 98 Notes 1 All dimensions are in inches unless otherwise specified 2 Finish Galvanized steel with light gray paint on front face 3 Net Weight without rectifiers List KG and Distribution Cabinet 38 75 lbs For 1 Row Dist Cabinet add 37 75 lbs For 2 Row Dist Cabinet add 74 25 lbs For List KG add 9 lbs 4 Overall Mounting Heig...

Page 126: ...pecified 2 P N 559806 tray shown P N 559807 and 559808 similar 3 4 Weight in LBS per tray less batteries 5 Finish Gray 6 Maximum trays available per rack is three 3 Tray P N Dimension A Dimension B Part No With Circuit Breaker Option Without Circuit Breaker Option 559806 9 781 22 44 559807 6 90 12 50 559808 10 48 23 14 559808 25 lbs 23 lbs 559806 33 lbs 29 lbs 559807 20 lbs 18 lbs 10 50 12 25 14 0...

Page 127: ...0 22 35 Tray P Ns 559809 559810 559811 559812 With Circuit Breaker Option 25 0 lbs 25 3 lbs 18 5 lbs 26 0 lbs Without Circuit Breaker Option 23 0 lbs 23 3 lbs 16 5 lbs 24 0 lbs ISO View Front View 10 50 12 25 14 00 as ordered A See Note 3 B See Note 3 Right Side View Notes 1 All dimensions are in inches unless otherwise specified 2 P N 559809 tray shown P Ns 559810 559811 and 559812 similar 3 5 Fi...

Page 128: ...9422 0858 Deka East Penn Mfg Co Inc Lyon Station PA 19536 0147 Douglas Douglas Battery Mfg Co 500 Battery Dr Winston Salem NC 27117 2159 Northstar NorthStar Battery Co LLC 4000 Continental Way Springfield MO 65803 PowerSafe EnersysTM EnerSys Inc Reading PA 196212 4145 RELATED DOCUMENTATION Installation Instructions Section 6025 User Instructions Section 6026 Rectifier User Instructions UM1R482000e...

Page 129: ...iv Group Corp All other names and logos referred toare tradenames trademarks or registered trademarks oftheir respective owners While every precaution has beentaken to ensure accuracy andcompleteness herein Vertiv Group Corp assumes no responsibility and disclaims all liability for damages resulting from use ofthis information or for any errors or omissions Specifications are subject to change wit...

Reviews: