M es s ag e 1
M es s ag e 2
M es s ag e 3
D efinition
LOAD ON INVERTER
TEST MODE ACTIVE
ALARM ACTIVE – WARNING
This system is in warning operating mode, supplied by
the inverter, running in a system test mode, and has an
active warning. This means the system is in TEST
MODE, and something was determined to be outside
normal test operations
LOAD ON BYPASS
TEST MODE ACTIVE
ALARM ACTIVE – WARNING
This system is in warning operating mode, supplied by
the bypass, running in a system test mode, and has an
active warning. This means the system is in TEST
MODE, and something was determined to be outside
normal test operation
LOAD ON BATTERY
TEST MODE ACTIVE
ALARM ACTIVE – WARNING
This system is in warning operating mode, supplied by
the battery, running in a system test mode, and has an
active warning. This means the system is in TEST
MODE, and something was determined to be outside
normal test operations
LOAD ON INVERTER
FREQUENCY CONVERTER
MODE ACTIVE
ALARM ACTIVE – WARNING
This system is in warning operating mode, supplied by
the inverter, operating as a frequency converter, and
has an active warning. This means the system is
operating, but something was determined to be outside
normal range
T able 5.2 W arn in g statu s m essages (co n tin u ed)
M es s ag e 1
M es s ag e 2
M es s ag e 3
D efinition
LOAD ON INVERTER
OUTPUT OVERLOAD
TRANSFER TO BYPASS
PENDING
This system is in critical operating mode, supplied by the
inverter, and the system can withstand specific duration
during overload conditions after that load will be
transferred to bypass
LOAD ON INVERTER
ALARM ACTIVE – CRITICAL
VIEW ALARM LOG FOR
DETAILS
This system is in critical operating mode, supplied by the
inverter. There is a critical fault in the system that the
user needs to view
LOAD ON BYPASS
LOAD AUTOMATICALLY
TRANSFERRED TO BYPASS
VIEW ALARM LOG FOR
DETAILS
This system is in critical operating mode, supplied by the
bypass. The system moved the load to the bypass due
to a critical fault in the system
LOAD ON BYPASS
ALARM ACTIVE – CRITICAL
VIEW ALARM LOG FOR
DETAILS
This system is in critical operating mode, supplied by the
bypass. The system is running on bypass not due to
auto- transfer, and a critical fault is active in the system
LOAD ON BATTERY
X MINUTES REMAINING
LOAD SHUTDOWN
IMMINENT
This system is in critical operating mode, supplied by the
inverter via the battery. The battery is extremely low
and the load will turn Off or transfer to bypass soon
LOAD OFF
ALARM ACTIVE – CRITICAL
VIEW ALARM LOG FOR
DETAILS
This system is in critical operating mode, load not
supplied by this unit. The load is not supplied for any
reason and a critical fault is active
LOAD OFF
/
/
This system is in critical operating mode, load not
supplied by this unit. The load is not supplied and no
active fault is present
T able 5.3 Critical statu s m essages
5 Operator Control and Display Panel
95
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM 0250kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Page 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...