6 Single UPS Operation Introduction
This chapter introduces the operating precautions and daily operating methods of UPS in detail.
6.1 Brief Introduction
6.1.1 Precautions
IM P O R T A N T ! T h e u ser can co n du ct relative o peratio n o n ly after th e au th o rized en gin eer carries o u t
th e first po wer o n an d test.
W A R N IN G ! Hazardo u s m ain s an d/o r battery vo ltage
1. N o o perato r-serviceable parts are lo cated beh in d co vers th at requ ire a to o l fo r th eir rem o val.
O n ly qu alified service perso n n el are au th o rized to rem o ve su ch co vers.
2. A n y o peratio n o n th e term in als sh all be perfo rm ed after 10 m in u tes o f UP S po wer-o ff an d
after verificatio n o f n o n -h azardo u s vo ltage.
1.
For the control keys and touch screen related to all the operating steps, refer to Operator Control and Display
Panel.
2.
During operation, the buzzer alarm may occur at any time. Press SILENCE ON/OFF key to silence the audible
alarm.
3.
When UPS uses traditional lead-acid battery, the system provides boost charge optional function. If the lead-
acid battery is used, when the mains returns after an extended mains failure, the charging voltage of the
battery will be higher than the normal charging voltage, this is normal, and the charging voltage of the battery
will return to normal value after a few hours' charging.
6 Single UPS Operation Introduction
101
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM 0250kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Page 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...