Inverter Off
The Inverter Off menu item is available whenever the UPS has input power and the inverter is Off. Before executing the
command, verify that the UPS and connected load are prepared for the inverter to be shut down.
N O T E: R isk o f im pro per o peratio n . Can cau se lo ad dro p resu ltin g in equ ipm en t dam age. T h e In verter
O ff will sh u t o ff po wer to th e co n n ected lo ad u n less bypass po wer is available. B efo re execu tin g th is
co m m an d, verify th at th e co n n ected lo ad is eith er sh u t o ff o r th at in pu t po wer to th e lo ad will be
su pplied by an o th er so u rce, su ch as bypass.
F igu re 5.18 In verter O ff co m m an d
5 Operator Control and Display Panel
73
Vertiv™ Liebert® APM Plus User Manual