6.2.2 Startup Procedures in ECO Mode
1.
Open the front door of the UPS, ensure that the internal maintenance bypass switch Q3 is disconnected, and
that the input cables and copper bars are reliably connected.
W A R N IN G ! In parallel UP S co n figu ratio n , all o peratio n s related to disco n n ectio n o r co n n ectio n
o f th e m ain ten an ce bypass switch sh all be execu ted with in th ree seco n ds to avo id o verlo ad
situ atio n s & dam age to th e m ain ten an ce bypass switch .
2.
Close the output switch Q5, bypass input switch Q2, rectifier input switch Q1, and all external output isolating
switches (if any) of the UPS in turn.
At the moment, the system is powered on, and the startup screen pops up.
3.
If ECO mode is required, contact Vertiv service engineer to set it through the setting software. If you wish to set
it by yourself, you can enable it through the sub-menu under 'SETUP' on the TOUCHSCREEN screen. For
details, refer to Operator Controls.
F igu re 6.6 Settin g ECO m o de
4. When the rectifier start process is finished, start the system according to Startup Procedures in Normal Mode.
After the inverter runs normally, if the bypass voltage is within the range of ECO power supply, then the system
works in ECO mode; otherwise the system will transfer to inverter. The system will automatically work in ECO
mode after the bypass voltage is within the range of ECO power supply and lasts for five minutes.
UPS operated in ECO mode
6 Single UPS Operation Introduction
107
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM 0250kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Page 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...