7.13 Battery Maintenance
For the battery maintenance and maintenance precautions, refer to IEEE-Std-1188-2005 and the relevant manuals provided
by the battery manufacturer.
N O T E:
1. P erio dically ch eck th e screws o f th e battery co n n ectio n parts an d co n firm th at th ey are firm ly
tigh ten ed. If th ere is an y lo o sen ed screw, tigh ten it im m ediately.
2. En su re th at all safety devices o perate n o rm ally, an d th at th e battery m an agem en t param eters
are set pro perly.
3. M easu re an d reco rd th e air tem peratu re in side th e battery ro o m .
4. Ch eck to en su re th at th e battery term in als h ave n o dam age o r h eat gen eratin g trace, an d th e
battery en clo su re an d term in al sh ields are in tact.
7.14 Disposal of Used Battery
If the battery has liquid leakage or is damaged, place the battery into the container that can withstand sulphuric acid and
discard it according to the local regulations.
Used lead acid storage battery belongs to dangerous waste, and it is a key item for used battery pollution control. The
storage, transportation, use and disposal of the battery shall comply with the national and local laws and regulations on
dangerous waste and used battery pollution prevention and other standards.
According to the relevant national regulations, the used lead acid storage battery must be recycled and shall not be
disposed of with other methods. Random discard or any other improper disposal of the used lead acid storage battery may
cause severe environmental pollution and the relevant person will be investigated for corresponding legal responsibilities.
7 Battery
132
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM 0250kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Page 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...