M es s ag e 1
M es s ag e 2
M es s ag e 3
D efinition
Load on inverter
Test mode active
Alarm active – Warning
This system is in warning operating mode, supplied by
the inverter, running in a system test mode, and has an
active warning. This means the system is in TEST
MODE, and something was determined to be outside
normal test operations
Load on bypass
Test mode active
Alarm active – Warning
This system is in warning operating mode, supplied by
the bypass, running in a system test mode, and has an
active warning. This means the system is in TEST
MODE, and something was determined to be outside
normal test operation
Load on battery
Test mode active
Alarm active – Warning
This system is in warning operating mode, supplied by
the battery, running in a system test mode, and has an
active warning. This means the system is in TEST
MODE, and something was determined to be outside
normal test operations
Load on inverter
Frequency converter mode
active
Alarm active – Warning
This system is in warning operating mode, supplied by
the inverter, operating as a frequency converter, and
has an active warning. This means the system is
operating, but something was determined to be outside
normal range
T able 5.2 W arn in g statu s m essages (co n tin u ed)
M es s ag e 1
M es s ag e 2
M es s ag e 3
D efinition
Load on inverter
Output overload
Transfer to bypass pending
This system is in critical operating mode, supplied by the
inverter, and system can withstand specific duration
during overload conditions after that load will be
transferred to bypass
Load on inverter
Alarm active – Critical
View alarm log for details
This system is in critical operating mode, supplied by the
inverter. There is a critical fault in the system that the
user needs to view
Load on bypass
Load Automatically
transferred to bypass
View alarm log for details
This system is in critical operating mode, supplied by the
bypass. The system moved the load to the bypass due
to a critical fault in the system
Load on bypass
Alarm active – Critical
View alarm log for details
This system is in critical operating mode, supplied by the
bypass. The system is running on bypass not due to
auto- transfer, and a critical fault is active in the system
Load on battery
X minutes remaining
Load shutdown imminent
This system is in critical operating mode, supplied by the
inverter via the battery. The battery is extremely low
and the load will turn Off or transfer to bypass soon
Load off
Alarm active – Critical
View alarm log for details
This system is in critical operating mode, load not
supplied by this unit. The load is not supplied for some
reason and a critical fault is active
Load off
/
/
This system is in critical operating mode, load not
supplied by this unit. The load is not supplied and no
active fault is present
T able 5.3 Critical statu s m essages
5 Touch Screen
98
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM Plus 0500kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 500 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 34: ...2 Overview 26 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 45: ...Four switches 500 kVA 3 Mechanical Installation 37 Vertiv Liebert APM Plus User Manual...
Page 76: ...Figure 5 11 Customize the display 5 Touch Screen 68 Vertiv Liebert APM Plus User Manual...
Page 86: ...Figure 5 20 Enable module redundancy 5 Touch Screen 78 Vertiv Liebert APM Plus User Manual...
Page 91: ...Figure 5 24 Status Gauge setting options 5 Touch Screen 83 Vertiv Liebert APM Plus User Manual...
Page 92: ...5 Touch Screen 84 Vertiv Liebert APM Plus User Manual...
Page 94: ...5 Touch Screen 86 Vertiv Liebert APM Plus User Manual...
Page 95: ...Figure 5 26 Unit status Bypass details 5 Touch Screen 87 Vertiv Liebert APM Plus User Manual...
Page 96: ...Figure 5 27 Unit status Battery details 5 Touch Screen 88 Vertiv Liebert APM Plus User Manual...
Page 97: ...Figure 5 28 Unit status Load details 5 Touch Screen 89 Vertiv Liebert APM Plus User Manual...
Page 100: ...5 Touch Screen 92 Vertiv Liebert APM Plus User Manual...
Page 112: ...5 Touch Screen 104 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 184: ...12 Specifications 176 This page intentionally left blank Vertiv Liebert APM Plus User Manual...