W A R N IN G ! High earth leak age cu rren t
1. Earth co n n ectio n is critical befo re co n n ectin g th e in pu t su pply (in clu din g bo th m ain s su pply
an d battery).
2. T h is equ ipm en t is in stalled with an EM C filter.
3. Earth leak age cu rren t is less th an 3000 m A .
4. T ran sien t an d steady state earth leak age cu rren ts, wh ich m ay o ccu r wh en th e equ ipm en t is
started, sh o u ld be tak en in to acco u n t in th e selectio n o f in stan tan eo u s R CCB s o r R CD devices.
5. R CCB wh ich is sen sitive to u n idirectio n al DC pu lse (class A ) an d in sen sitive to tran sien t state
cu rren t pu lse m u st be selected.
6. N o te also th at th e earth leak age cu rren ts o f th e lo ad will be carried by th e R CCB s o r R CDs.
7. T h e equ ipm en t m u st be earth ed in acco rdan ce with th e lo cal electrical co de o f practice.
W A R N IN G ! B ack feedin g pro tectio n
T h is UP S is fitted with a dry co n tact clo su re sign al fo r u se with an extern al au to m atic
disco n n ect device (su pplied by o th ers) to pro tect again st back feedin g vo ltage in to th e
in co m in g term in al th ro u gh th e rectifier o r bypass static switch circu it. A label m u st be added at
all extern al in co m in g prim ary su pply disco n n ect device to warn service perso n n el th at th e circu it
is co n n ected to th e UP S. T h e text o f th e label h as th e fo llo win g m ean in g: R isk o f vo ltage
back feed! Iso late th e UP S, th en ch eck fo r h azardo u s vo ltage between all term in als in clu din g th e
pro tective earth befo re wo rk in g o n th is circu it.
W A R N IN G ! T h e selectio n o f th e u pstream distribu tio n pro tectio n equ ipm en t o f th e UP S sh all
be selected in acco rdan ce with th e lo cal electrical regu latio n s.
1 Important Safety Instructions
iii
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM Plus 0500kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 500 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 34: ...2 Overview 26 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 45: ...Four switches 500 kVA 3 Mechanical Installation 37 Vertiv Liebert APM Plus User Manual...
Page 76: ...Figure 5 11 Customize the display 5 Touch Screen 68 Vertiv Liebert APM Plus User Manual...
Page 86: ...Figure 5 20 Enable module redundancy 5 Touch Screen 78 Vertiv Liebert APM Plus User Manual...
Page 91: ...Figure 5 24 Status Gauge setting options 5 Touch Screen 83 Vertiv Liebert APM Plus User Manual...
Page 92: ...5 Touch Screen 84 Vertiv Liebert APM Plus User Manual...
Page 94: ...5 Touch Screen 86 Vertiv Liebert APM Plus User Manual...
Page 95: ...Figure 5 26 Unit status Bypass details 5 Touch Screen 87 Vertiv Liebert APM Plus User Manual...
Page 96: ...Figure 5 27 Unit status Battery details 5 Touch Screen 88 Vertiv Liebert APM Plus User Manual...
Page 97: ...Figure 5 28 Unit status Load details 5 Touch Screen 89 Vertiv Liebert APM Plus User Manual...
Page 100: ...5 Touch Screen 92 Vertiv Liebert APM Plus User Manual...
Page 112: ...5 Touch Screen 104 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 184: ...12 Specifications 176 This page intentionally left blank Vertiv Liebert APM Plus User Manual...