A larm
E xp lanation
BCB1 Open
BCB1 state (open)
Phase A Out. Fuse Fail
Check that the wire jumper on the X3 board is correct
Phase B Out. Fuse Fail
Check that the wire jumper on the X3 board is correct
Phase C Out. Fuse Fail
Check that the wire jumper on the X3 board is correct
Equalize Chg. Timeout
The actual float charging time exceeds the time set by the setting software
MonCAN Comm. Abnor.
Communication failure among internal monitoring board and inverter, rectifier, and bypass
ParaMonCAN Comm.Abnor.
Communication fault between racks
PowerCAN Comm. Abnor.
Communication failure among inverter, rectifier and bypass
ParaPowerCANCommAbnor.
Communication failure between different UPSs in parallel system. Check if any UPS is not powered on or parallel cables
are not well connected, then clear the fault to restart the UPS
Discr.Bus Comm.Abnor.
Communication failure between discrete bus inside the rack. It is recommended to confirm that the rear communication
cables connection inside the rack is reliable
ParaDiscrBusCommAbnor.
Communication failure between discrete bus inside the rack. It is recommended to confirm that the rear communication
cables connection inside each rack is reliable, and that the bypass module is fixed
Ambient Overtemp.
The overtemperature detection of ambient temperature, which can be set through the setting software
Byp. SCR Fan Abnormal
The internal fan of bypass module is faulty
Top-outlet Fan Abnor.
The fan of top air outlet is faulty
System Interrupt Xfer
Execute the interval transfer under conditions of bypass unable to trace and inverter phase not locked
Para. Cable Abnormal
Parallel cables are not well connected, or the cables are damaged
LBS Cable Abnormal
LBS cables are not well connected, or the cables are damaged
Loss of Redundancy
Loss of redundant capacity
Pwr. Hardware Mismatch
The model information set at the host is inconsistent with the actual situation
Module Overtemp.
The power tubes of rectifier and inverter inside the module have overtemperature
Charger Overtemp.
The power tube of charger inside the module has overtemperature
T able 5.4 A larm list (co n tin u ed)
N O T E: 1. F o r UP S in stalled with th e o ptio n al battery m o n ito r, refer to th e u ser m an u al o f th e battery
m o n ito r fo r th e alarm m essages related to battery cell an d ch arge cu rren t.
N O T E: 2. If th e alarm is cau sed th ro u gh settin g th e so ftware valu e by Vertiv au th o rized en gin eer, an d
yo u wish to ch an ge th e settin g valu es, please co n tact th e Vertiv lo cal cu sto m er service cen ter.
5 Touch Screen
103
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM Plus 0500kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 500 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 34: ...2 Overview 26 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 45: ...Four switches 500 kVA 3 Mechanical Installation 37 Vertiv Liebert APM Plus User Manual...
Page 76: ...Figure 5 11 Customize the display 5 Touch Screen 68 Vertiv Liebert APM Plus User Manual...
Page 86: ...Figure 5 20 Enable module redundancy 5 Touch Screen 78 Vertiv Liebert APM Plus User Manual...
Page 91: ...Figure 5 24 Status Gauge setting options 5 Touch Screen 83 Vertiv Liebert APM Plus User Manual...
Page 92: ...5 Touch Screen 84 Vertiv Liebert APM Plus User Manual...
Page 94: ...5 Touch Screen 86 Vertiv Liebert APM Plus User Manual...
Page 95: ...Figure 5 26 Unit status Bypass details 5 Touch Screen 87 Vertiv Liebert APM Plus User Manual...
Page 96: ...Figure 5 27 Unit status Battery details 5 Touch Screen 88 Vertiv Liebert APM Plus User Manual...
Page 97: ...Figure 5 28 Unit status Load details 5 Touch Screen 89 Vertiv Liebert APM Plus User Manual...
Page 100: ...5 Touch Screen 92 Vertiv Liebert APM Plus User Manual...
Page 112: ...5 Touch Screen 104 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 184: ...12 Specifications 176 This page intentionally left blank Vertiv Liebert APM Plus User Manual...