6.4 Battery Test Procedures
The battery test function is disabled by default. If you need this function, please contact the customer service engineer of
Vertiv.
The battery self-test includes periodical self-test and manual maintenance self-test. When the load factor is 0~20%, the
system only supports manual maintenance self-test; when the load factor is 20% to 100%, the system supports periodical
self-test and manual maintenance self-test. The battery discharges 20% of total battery energy.
Periodical self-test is to test the battery activity. The periodical self-test is regular, and the self-test period can be
configured via the Vertiv software setting. During the periodical self-test, if the battery maintenance requirement is met, the
system will generate audible/visual alarm and corresponding records. The periodical self-test does not update the battery
curve table.
The mode of the manual maintenance self-test is similar to that of the periodical self-test, except for the maintenance self-
test mode is started manually, and this operation is valid only one time, that is the system will not automatically start up the
self-test once you exit. When the load factor is 20%~100%, during the maintenance self-test, if the battery maintenance
requirement is satisfied, the system will generate audible/visual alarm and corresponding records. The maintenance self-
test does not update the battery curve table.
N O T E: T h e perio dical self-test sh o u ld satisfy th e co n ditio n s o f battery flo at ch arge at least 5h , an d
gen erato r n o t co n n ected, wh ile th e m an u al m ain ten an ce self-test ju st satisfies th e co n ditio n s o f
battery fu lly ch arged.
Method
1.
Manual maintenance self-test: via the TOUCH SCREEN.
2.
Periodical self-test: self-test period can be configured via the Vertiv software setting. The range of battery self-
test period is 30 days to 360 days (default: 60 days).
Self-test startup conditions
1.
System load rate is within 0 to 20% (manual maintenance self-test) or 20% to 100% (periodical self-test), stable
output.
2.
Battery in fully charged state, battery float charge at least 5h, and generator not connected.
3.
Current system is in float charge state.
Self-test exit conditions
1.
Confirm that the system is not in self-test state at least 10 seconds, and satisfies the following conditions: in
battery mode or rectifier is closed, and then the system will shift to battery supply state.
2.
During the self-test, the system will shift to float charge state if the load fluctuation, UPS module overload, or no
battery occurs.
3.
During the self-test, if the battery voltage is lower than the calculated pre-alarm voltage, or the battery
discharge exceeds the protection time, then the system will shift to float charge state.
4. The user can manually stop the maintenance test via the TOUCH SCREEN.
5.
During the manual maintenance self-test, when the load rate ranges from 0 to 20%, the system will shift to float
charge state after the battery discharge for 5 min.
N O T E: A fter th e self-test is su ccessfu l, th e system will fu lly clear th e self-test in terval co u n ter. If th e
self-test fails th is tim e, th en exits th e system ; wh en self-test co n ditio n s are satisfied again , en ters self-
test o n ce m o re.
6 Single UPS Operation Introduction
117
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM Plus 0500kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 500 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 34: ...2 Overview 26 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 45: ...Four switches 500 kVA 3 Mechanical Installation 37 Vertiv Liebert APM Plus User Manual...
Page 76: ...Figure 5 11 Customize the display 5 Touch Screen 68 Vertiv Liebert APM Plus User Manual...
Page 86: ...Figure 5 20 Enable module redundancy 5 Touch Screen 78 Vertiv Liebert APM Plus User Manual...
Page 91: ...Figure 5 24 Status Gauge setting options 5 Touch Screen 83 Vertiv Liebert APM Plus User Manual...
Page 92: ...5 Touch Screen 84 Vertiv Liebert APM Plus User Manual...
Page 94: ...5 Touch Screen 86 Vertiv Liebert APM Plus User Manual...
Page 95: ...Figure 5 26 Unit status Bypass details 5 Touch Screen 87 Vertiv Liebert APM Plus User Manual...
Page 96: ...Figure 5 27 Unit status Battery details 5 Touch Screen 88 Vertiv Liebert APM Plus User Manual...
Page 97: ...Figure 5 28 Unit status Load details 5 Touch Screen 89 Vertiv Liebert APM Plus User Manual...
Page 100: ...5 Touch Screen 92 Vertiv Liebert APM Plus User Manual...
Page 112: ...5 Touch Screen 104 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 184: ...12 Specifications 176 This page intentionally left blank Vertiv Liebert APM Plus User Manual...