2.2.2 Bypass
Through the intelligent control of the ‘Static Switch’ module (as shown in Figure 2.1 on page 10) containing the controllable
electronic switch, the loads can be supplied by the inverter or the bypass. In normal situation, the loads are supplied by the
inverter, in that case the automatic inverter switch at inverter side is closed. In the case of overload (the overload delay time
expires) or inverter failure, the automatic inverter switch is opened, and the Static Switch module will automatically transfer
the loads to the bypass.
In normal operating state, to realize the uninterrupted transfer between inverter and bypass, the inverter output must be
synchronized with the bypass.
Therefore, when the bypass frequency is within the synchronization range, the inverter control circuit will synchronize the
inverter output frequency with the bypass frequency and phase.
Besides, the UPS has a manual maintenance bypass switch (without switch excluded) for shutdown of the UPS upon
maintenance. In this situation, the bypass will directly supply the critical loads through the maintenance bypass.
N O T E: W h en th e lo ad is su pplied by th e bypass o r m ain ten an ce bypass, th e qu ality o f th e po wer su pply
will be u n certain .
2.2.3 System Control Principle
Normal operation
Normal mode: It means that the UPS has normal input mains, the rectifier and inverter operate normally, the load is supplied
by the inverter, the battery circuit breaker is closed, and the battery is in stable floating charge state.
(Parallel System)
As the UPS single module outputs are connected in parallel, the system checks that the inverter control
circuits are perfectly synchronized with one another and with the bypass in terms of both frequency and phase, and that
they have the same output voltages. Current supplied to the load is automatically divided among UPSs. A warning message
appears while synchronization is in progress.
Mains abnormal
When the mains fails or is abnormal, the rectifier will stop working automatically, and the system will transfer to battery
output (through inverter). The length of the operation time in battery mode depends on the load and the battery capacity.
During this period, if the battery voltage falls to the EOD voltage and the mains still has not been recovered, the inverter will
stop working automatically, and the UPS touch screen will display corresponding alarm messages. If the system uses split
bypass configuration and the bypass is normal, the system will transfer to bypass.
Mains recovery
When the mains resumes normal within allowable time, the rectifier will start automatically and supply the load and charge
the battery again. Therefore, the power supply to the load will not be interrupted.
Battery disconnection
To disconnect the external battery from the UPS system for maintenance, use the external isolating switch. At this time,
except for the battery backup function upon mains failure, other functions and all the steady state performance of the UPS
will not be affected.
2 Overview
13
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM Plus 0500kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 500 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 34: ...2 Overview 26 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 45: ...Four switches 500 kVA 3 Mechanical Installation 37 Vertiv Liebert APM Plus User Manual...
Page 76: ...Figure 5 11 Customize the display 5 Touch Screen 68 Vertiv Liebert APM Plus User Manual...
Page 86: ...Figure 5 20 Enable module redundancy 5 Touch Screen 78 Vertiv Liebert APM Plus User Manual...
Page 91: ...Figure 5 24 Status Gauge setting options 5 Touch Screen 83 Vertiv Liebert APM Plus User Manual...
Page 92: ...5 Touch Screen 84 Vertiv Liebert APM Plus User Manual...
Page 94: ...5 Touch Screen 86 Vertiv Liebert APM Plus User Manual...
Page 95: ...Figure 5 26 Unit status Bypass details 5 Touch Screen 87 Vertiv Liebert APM Plus User Manual...
Page 96: ...Figure 5 27 Unit status Battery details 5 Touch Screen 88 Vertiv Liebert APM Plus User Manual...
Page 97: ...Figure 5 28 Unit status Load details 5 Touch Screen 89 Vertiv Liebert APM Plus User Manual...
Page 100: ...5 Touch Screen 92 Vertiv Liebert APM Plus User Manual...
Page 112: ...5 Touch Screen 104 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 184: ...12 Specifications 176 This page intentionally left blank Vertiv Liebert APM Plus User Manual...