3.6.2 Battery Location Selection
Batteries generate some amount of hydrogen and oxygen at the end of charge, so the fresh air volume of the battery
installation environment must meet the EN50272-2001 requirements.
The ambient temperature is the main factor that affects the battery capacity and life. The normal operating temperature of
the battery is 20 °C. If the ambient temperature is higher than 20°C, the battery life will be reduced. If it is lower than 20 °C,
the battery capacity will be reduced. In normal situation, the allowable ambient temperature for the battery is 15 °C to 25 °C.
The ambient temperature of the battery shall be maintained constant, and the battery shall be kept away from heat source
and air outlet.
Battery can be installed inside the specialized battery cabinet which shall be close to the UPS. If the battery is placed on
the raised floor, bracket shall be installed under the floor, just as for the UPS. If the battery adopts rack mounting or is
mounted far from the UPS with other installation mode, the battery circuit breaker shall be installed near the battery, and
the cabling distance shall be minimized.
3.6.3 Storage
If the UPS is not installed immediately, it must be stored with the original packaging in a room for protection against
excessive humidity and heat sources (see Table 12.2 on page 171). The battery should be stored in a dry and cool place with
good ventilation. The most suitable storage temperature ranges from 20 °C to 25 °C.
W A R N IN G ! Du rin g battery sto rage, perio dically ch arge th e battery acco rdin g to th e battery
m an u factu rer in stru ctio n s. In th e ch arge pro cess, tem po rarily co n n ect th e UP S to th e m ain s
an d activate th e battery by rech argin g th e battery.
3 Mechanical Installation
33
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM Plus 0500kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 500 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 34: ...2 Overview 26 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 45: ...Four switches 500 kVA 3 Mechanical Installation 37 Vertiv Liebert APM Plus User Manual...
Page 76: ...Figure 5 11 Customize the display 5 Touch Screen 68 Vertiv Liebert APM Plus User Manual...
Page 86: ...Figure 5 20 Enable module redundancy 5 Touch Screen 78 Vertiv Liebert APM Plus User Manual...
Page 91: ...Figure 5 24 Status Gauge setting options 5 Touch Screen 83 Vertiv Liebert APM Plus User Manual...
Page 92: ...5 Touch Screen 84 Vertiv Liebert APM Plus User Manual...
Page 94: ...5 Touch Screen 86 Vertiv Liebert APM Plus User Manual...
Page 95: ...Figure 5 26 Unit status Bypass details 5 Touch Screen 87 Vertiv Liebert APM Plus User Manual...
Page 96: ...Figure 5 27 Unit status Battery details 5 Touch Screen 88 Vertiv Liebert APM Plus User Manual...
Page 97: ...Figure 5 28 Unit status Load details 5 Touch Screen 89 Vertiv Liebert APM Plus User Manual...
Page 100: ...5 Touch Screen 92 Vertiv Liebert APM Plus User Manual...
Page 112: ...5 Touch Screen 104 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 184: ...12 Specifications 176 This page intentionally left blank Vertiv Liebert APM Plus User Manual...