Pin
N am e
M eaning s
Pin
N am e
M eaning s
17
GND_DRY
External maintenance
isolation switch status (24
V/10 mA rated); Pin17 /Pin19
open for QOP closed.
Configurable input dry
contact 2:
0) Undefined
1) Battery fault
2) External maintenance
isolation switch closed
(default)
3) ECO mode disabled
4) Charger to be shut down
5) BCB tripping
6) Transfer to inverter
disabled
7) Battery maintenance self-
check starts
8) Battery maintenance self-
check ends
9) Alarm cleared
10) Battery alarm
11) Battery low-voltage alarm
18
Configurable input
dry contact 3 J7-
18/20
Charger shutdown (24 V/10 mA rated).
Pin18/Pin20 shorted for charger off
command.
0) Undefined
1) Battery fault
2) External maintenance isolation switch
closed (default)
3) ECO mode disabled
4) Charger to be shut down
5) BCB tripping
6) Transfer to inverter disabled
7) Battery maintenance self-check starts
8) Battery maintenance self-check ends
9) Alarm cleared
10) Battery alarm
11) Battery low-voltage alarm
19
Configurable input dry
contact 2 J7-17/19
20
GND_DRY
21
TMP_ENV_dry
Ambient temperature
detection
22
Configurable input
dry contact 3 J7-
22/24
External output switch status (24 V/10 mA
rated); Pin22/Pin24 open for QE closed.
0) Undefined
1) Battery fault
2) External maintenance isolation switch
closed (default)
3) ECO mode disabled
4) Charger to be shut down
5) BCB tripping
6) Transfer to inverter disabled
7) Battery maintenance self-check starts
8) Battery maintenance self-check ends
9) Alarm cleared
10) Battery alarm
11) Battery low-voltage alarm
23
GND_DRY
24
GND_DRY
T able 4.5 Descriptio n o f dry co n tact po rt J 7 (co n tin u ed)
4 Electrical Installation
51
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM Plus 0500kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 500 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 34: ...2 Overview 26 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 45: ...Four switches 500 kVA 3 Mechanical Installation 37 Vertiv Liebert APM Plus User Manual...
Page 76: ...Figure 5 11 Customize the display 5 Touch Screen 68 Vertiv Liebert APM Plus User Manual...
Page 86: ...Figure 5 20 Enable module redundancy 5 Touch Screen 78 Vertiv Liebert APM Plus User Manual...
Page 91: ...Figure 5 24 Status Gauge setting options 5 Touch Screen 83 Vertiv Liebert APM Plus User Manual...
Page 92: ...5 Touch Screen 84 Vertiv Liebert APM Plus User Manual...
Page 94: ...5 Touch Screen 86 Vertiv Liebert APM Plus User Manual...
Page 95: ...Figure 5 26 Unit status Bypass details 5 Touch Screen 87 Vertiv Liebert APM Plus User Manual...
Page 96: ...Figure 5 27 Unit status Battery details 5 Touch Screen 88 Vertiv Liebert APM Plus User Manual...
Page 97: ...Figure 5 28 Unit status Load details 5 Touch Screen 89 Vertiv Liebert APM Plus User Manual...
Page 100: ...5 Touch Screen 92 Vertiv Liebert APM Plus User Manual...
Page 112: ...5 Touch Screen 104 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 184: ...12 Specifications 176 This page intentionally left blank Vertiv Liebert APM Plus User Manual...