122 Chapter 8 Options
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Warning
1. Only Vertiv authorized engineers shall carry out the installation.
2. Carry out the installation strictly following the instructions. Failure to observe this could cause personnel injury or
damage to the UPS and seismic anchor kits.
Preparation
1. Prepare the installation tools, including a cross head screwdriver, a torque spanner and an adjustable
spanner.
2. Check that all installation materials are present and complete, including four seismic anchors, 36 M6 ×
20 tapping screws, eight M12 expansion bolts.
Procedures
The installation procedures are as follows:
1. Lift up the UPS cabinet, and upraise the four feet, then remove the rear mechanical part, see Figure 8-11.
Rear mechanical part
Foot (4 pcs)
Figure 8-11 Removing adjustable feet
2. Use M6 × 20 tapping screws (18 pcs) to install seismic anchor 1 and seismic anchor 2 on the rear
bottom of the UPS cabinet, as shown in Figure 8-12.
M6*20 tapping screw
Seismic anchor 1
Seismic anchor 2
Figure 8-12 Installing seismic anchor 1 and seismic anchor 2
3. As shown in Figure 8-13, use four M12 expansion bolts to fix seismic anchor 3 on the ground, then push
the UPS backward to insert seismic anchor 1 and seismic anchor 2 into the two holes of seismic anchor 3
respectively.