20 Chapter 3 Electrical Installation
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Table 3-1 Max. steady state AC and DC currents
UPS power
(kVA)
Rated current (A)
Bus stud bolt/nut specification
Max.
input
current
1,2
Output/bypass
current
2
at full load
Battery discharge
current (+, -, N) at
min. battery voltage
Input/battery/
output/
bypass/PE
cable
Recommende
d torque (N.m)
380V
400
V
415V
80kVA
163
121
116
111
292
M10
22
±10%
100kVA
204
152
145
139
365
M10
22
±10%
120kVA
245
182
174
167
439
M10
22
±10%
160kVA
356
242
232
222
585
M10
22
±10%
200kVA
408
303
290
278
731
M10
22
±10%
1. Max. input current is calculated according to the low voltage input of 176V and 100% load percentage.
2. Max. output/bypass current is calculated according to the rated voltage and 100% load percentage.
3. The battery discharge current at the lowest battery voltage is calculated according to the battery cell number of 30
and lowest EOD voltage of1.6V.
3.1.3
Recommended CSA Of UPS Cable
The recommended CSA of the UPS cable is listed in Table 3-2.
Table 3-2 Recommended CSA of the UPS cable (unit: mm2, ambient temperature: 25°C)
Model
Input
Output
Bypass
Neutral line
Earth cable
Battery
80kVA
50
35
35
50
25
See Table 6-4
100kVA
70
50
50
70
35
See Table 6-4
120kVA
95
70
70
95
50
See Table 6-4
160kVA
2*50
95
95
2*50
50
See Table 6-4
200kVA
2*70
2*50
2*50
2*70
70
See Table 6-4
3.1.4
Selection Of UPS I/O And Battery Switch
The user can select the switch according to actual needs. Refer to Table 3-1 for I/O current and battery
current value.
3.1.5
Distance Between The UPS Connection Point And The Floor
Table 3-3 Min. distance between UPS connection point and floor
UPS connection point
Min. distance
(
mm
)
80kVA ~ 120kVA
160kVA ~ 200kVA
Rectifier input
350
294
Bypass input
431
385
AC Output
383
294
Battery supply
387
321
PE terminal
506
370
3.1.6
Notes
The following points are for general guidance only. If there are relevant local regulations, the local
regulations shall prevail.