Chapter 3 Electrical Installation 25
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Note:
Step 1: Remove the left top cover, make holes according to the cables number and size, and
lead cables from mains, bypass, and PE into the cabinet through the holes, then
connect them to corresponding terminals.
Step 2: Remove the right top cover, make holes according to the cables number and size, then
lead the battery cables and output cables from corresponding terminals out of the cabinet.
Step 1
Step 2
Figure 3-3
Power cables wiring route of 80kVA ~ 120kVA (top cable access)