Chapter 3 Electrical Installation 27
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Step
Note:
Step: Remove the bottom plate, make holes according to the cables number and size, and lead
cables into the cabinet through the holes, then connect them to corresponding terminals.
Figure 3-5 Power cables wiring route of 160kVA ~ 200kVA (bottom cable access)
Warning
Before cables connection, make sure that all external and internal power switches of the UPS are off, and post
necessary warning signs to prevent inadvertent operation of the switches. Meanwhile, measure the voltages
between the UPS terminals and the voltages between the terminals and the earth.