66 Chapter 4 Operator Control And Display Panel
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Message 1
Message 2
Message 3
Definition
LOAD ON
BATTERY
TEST MODE
ACTIVE
ALARM
ACTIVE –
WARNING
This system is in warning operating mode,
supplied by the battery, running in a system test
mode, and has an active warning. This means the
system is in TEST MODE, and something was
determined to be outside normal test operations
LOAD ON
INVERTER
FREQUENCY
CONVERTER
MODE
ACTIVE
ALARM
ACTIVE –
WARNING
This system is in warning operating mode,
supplied by the inverter, operating as a frequency
converter, and has an active warning. This means
the system is operating, but something was
determined to be outside normal range
Table 4-3
Critical status messages
Message 1
Message 2
Message 3
Definition
LOAD ON
INVERTER
OUTPUT
OVERLOAD
TRANSFER TO
BYPASS
PENDING
This system is in critical operating mode, supplied
by the inverter, and the load is about to be
transferred to the bypass due to overload
timeouts
LOAD ON
INVERTER
ALARM
ACTIVE –
CRITICAL
VIEW ALARM
LOG FOR
DETAILS
This system is in critical operating mode, supplied
by the inverter. There is a critical fault in the
system that the user needs to view
LOAD ON
BYPASS
LOAD
AUTOMATI
CALLY
TRANSFERR
ED TO
BYPASS
VIEW ALARM
LOG FOR
DETAILS
This system is in critical operating mode, supplied
by the bypass. The system moved the load to the
bypass due to a critical fault in the system
LOAD ON
BYPASS
ALARM
ACTIVE –
CRITICAL
VIEW ALARM
LOG FOR
DETAILS
This system is in critical operating mode, supplied
by the bypass. The system is running on bypass
not due to auto- transfer, and a critical fault is
active in the system
LOAD ON
BATTERY
X
MIN
UTE
S
REM
AINI
NG
LOAD
SHUTDOWN
IMMINENT
This system is in critical operating mode, supplied
by the inverter via the battery. The battery is
extremely low and the load will turn Off or
transfer to bypass soon
LOAD OFF
ALARM
ACTIVE –
CRITICAL
VIEW ALARM
LOG FOR
DETAILS
This system is in critical operating mode, load not
supplied by this unit. The load is not supplied for
any reason and a critical fault is active
LOAD OFF
—
—
This system is in critical operating mode, load not
supplied by this unit. The load is not supplied and
no active fault is present
LOAD ON
BATTERY
ALARM
ACTIVE –
CRITICAL
VIEW ALARM
LOG FOR
DETAILS
This system is in critical operating mode, supplied
by the battery. The system is running on inverter
via the battery, is not in imminent shutdown and a
critical fault is active in the system
LOAD OFF
SERVICE
MODE
ACTIVE
—
This system is Off with a service mode active
LOAD ON
INVERTER
ENERGY
SAVING
MODE
ACTIVE
ALARM
ACTIVE –
CRITICAL
This system is in critical operating mode, supplied
by the inverter. The system is running on inverter,
with an energy saving mode active and a critical
fault is active in the system
LOAD ON
BYPASS
ENERGY
SAVING
MODE
ACTIVE
ALARM
ACTIVE –
CRITICAL
This system is in critical operating mode, supplied
by the bypass. The system is running on bypass,
with an energy saving mode active and a critical
fault is active in the system
LOAD OFF
ENERGY
SAVING
ALARM
ACTIVE –
This system is in critical operating mode. The