98 Chapter 6 Battery
Liebert EXM 80kVA ~ 200kVA UPS User Manual
6.13
Battery Temperature Sensor (Option)
Vertiv provides an optional battery temperature sensor. Conect the battery temperature sensor as shown
in Figure 6-9.
To bypass module J22
Brown
Black
Red
Battery temperature sensor 0
~
4 pcs, if one is selected, then
connect X103 of C2 board; if two, then connect X103 and
X104, and so on.
Figure 6-9 Wiring of battery temperature sensor
6.14
Battery Maintenance
For the battery maintenance and maintenance precautions, refer to IEEE-Std-1188-2005 and the relevant
manuals provided by the battery manufacturer.
Note
1. Periodically check the screws of the battery connection parts and confirm that they are firmly tightened. If there is
any loosened screw, tighten it immediately.
2. Ensure that all safety devices operate normally, and that the battery management parameters are set properly.
3. Measure and record the air temperature inside the battery room.
4. Check to ensure that the battery terminals have no damage or heat generating trace, and the battery enclosure
and terminal shields are intact.
6.15
Disposal Of Used Battery
If the battery has liquid leakage or is damaged, place the battery into the container that can withstand
sulphuric acid and discard it according to the local regulations.