Chapter 3 Electrical Installation 35
Liebert EXM 80kVA ~ 200kVA UPS User Manual
3.2.9
Intellislot Port
The Intellislot ports are used for installing optional cards on the site, including
IS-UNITY-DP card,
IS-Relay
card, and SIC card. Table 3-9 provides models and installation positions of the optional cards. For the
detailed installation of the optional cards, refer to the corresponding contents in
Chapter 8 Options
.
Table 3-9
Models and installation positions of optional cards
Optional card
Model
Installation position
IS-UNITY-DP card
IS-UNITY-DP
Intellislot ports 1 ~ 3 (port 1 or 2 recommended)
SIC card
UF-SNMP810
Intellislot ports 1 ~ 3 (port 1 or 2 recommended)
IS-Relay card
IS-RELAY
Intellislot port 1
Note
1. The Intellislot port 2 shares communication resource with RS485 port. To avoid conflict, when using RS485 port in
service and commissioning, it is not recommended to use the Intellislot port 2.
2. The Intellislot port 3 shares communication resource with RS232 port. To avoid conflict, when using RS232 port in
service and commissioning, it is not recommended to use the Intellislot port 3.
3.2.10
Signal Cable Connection Steps
Note
Respectively route the power cables and signal cables. The shielding coat of signal cable must be reliably earthed.
Two connection modes are available: top cable access, bottom cable access. See Figure 3-13 to Figure
3-16.