Chapter 4 Operator Control And Display Panel 41
Liebert EXM 80kVA ~ 200kVA UPS User Manual
4.2
Navigating Through The Liebert EXM Touchscreen Control Panel
The Liebert EXM Touchscreen Control Panel is active whenever the UPS has input power. The
touchscreen TOUCHSCREEN on the front of the UPS permits:
• Logging in to the system
--
4.3.1 Log In to the Liebert EXM Touchscreen Control Panel
• Customizing the user interface
--
4.3.2 Customizing the Display
• Checking the status of the UPS and its external batteries, including all measured parameters, events and
alarms--
4.4 Viewing UPS Status
and
4.5 Viewing UPS Component Status
• Silencing alarms
--Silence an Alarm
• Turning the UPS On
--Inverter On
• Turning the UPS Off
--Inverter Off
• Resetting faults
--Reset Fault
• Enabling Energy Saving Mode
--Energy Saving Mode Activation
The Liebert EXM Touchscreen Control Panel's display default view is two panes: One-line animated mimic
and UNIT STATUS. The appearance can be changed to multiple panes that show other data. Customizing
the appearance is detailed in
4.3.2 Customizing the Display
.
4.2.1
Access Level Log-In
The Liebert EXM Touchscreen Control Panel provides security by limiting the authority to change how
the UPS operates. Each of the four access levels offers different authority:
• Observer
--Viewing permission only; can choose graphic or text display; no PIN required
• Operator
--Permission to start the UPS, shut the system down, reset faults and enable or disable Eco
Mode operation; PIN required
• Administrator
--All functions of Operator plus permission to change PINs for Operator and Administrator
level; PIN required
• Service
--All functions of Administrator plus permission to alter system configuration, choose serial
communication protocol, enable equalize battery charging and change Service PIN; PIN required.
Vertiv Tech Liebert Services sets PINs when setting up the UPS. These default PINs may be changed by
those with Administrator or Service access (see above).
Default PINs are:
• Operator: 1234
• Administrator: 2345
Note
Risk of unauthorized changes to operational settings. Can cause equipment damage. The default PIN numbers
should be changed immediately to prevent unauthorized personnel from changing UPS operation or even shutting
down the UPS. The PINs for Operator and Administrator may be changed by logging in with either Administrator or
Service level access.