Installation Drawings
Vertiv
| Liebert
®
EXM
™
Parallel Cabinet User Manual |
19
Figure 7
Main components—800mm 1+1 and 2+0 Liebert EXM Parallel Cabinet
1.65"
(42mm)
1.65"
(42mm)
0.71"
(18mm)
0.55"
(14mm)
∅
0.56"
(14mm)
∅
0.44"
(11mm)
∅
0.56"
(14mm)
∅
0.56"
(14mm)
1.75"
(44mm)
1.75" (44mm)
1.75"
(44mm)
1.26"
(32mm)
18.3"
(465mm)
18.5"
(470mm)
16.9"
(429mm)
62.9"
(1598mm)
58.6"
(1488mm)
20.5"
(521mm)
MBB
MIB
MOB2
MOB1
(See DETAIL C)
Main Input Busbar
(See DETAIL A)
Bypass Input Busbar
(See DETAIL A)
Neutral Busbar
(See DETAIL B)
Ground Busbar
(See DETAIL D)
0.61"
(15mm)
1.75"
(44mm)
SIDE VIEW
With Panel Removed
FRONT VIEW
With Door Removed
ISOMETRIC
VIEW
DETAIL B
DETAIL A
DETAIL C
DETAIL D
1.69" (43mm)
Typically
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. All wiring is to be in accordance with national and local electrical codes.
4. If maintenance bypass cabinet is attached to UPS, Vertiv will supply
the interconnection cables.
5. 1+1 available from 120-200 kVA, 2+0 available from 120-160 kVA.
EXM16109
Rev. 2