Installation Drawings
Vertiv
| Liebert
®
EXM
™
Parallel Cabinet User Manual |
21
Figure 9
Outline drawing—600mm Liebert EXM Parallel Cabinet
23.6"
(600mm)
NOTES
1. 24" (610) minimum clearance above unit for air exhaust.
36" (914) front access required for service.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wiring must be run in separate conduits.
6. Copper cables only are recommended.
7. All wiring is to be in accordance with national and local electrical codes.
BOTTOM VIEW
TOP VIEW
RIGHT SIDE VIEW
DETAIL A
FRONT VIEW
Cable Entry Area
20.7" x 17.7"
(526mm x 450mm)
Control Cable Entry
5.9" x 2"
(150mm x 51mm)
Control Cable Entry
4.7" x 1.6"
(119mm x 41mm)
Cable Entry Area
20.7" x 16.9"
(526mm x 429mm)
39.8" (1010mm)
Caster
Leveler
EXM12012A
Pg. 1, Rev. 3
78.7"
(2000mm)
20.4"
(518mm)
34.3"
(872mm)
28.3"
(719mm)
Brkt.
Centers
2.9" (74mm)
15.0"
(381mm)
FRONT
4.5"
(114mm)
18.5"
(470mm)
1.8"
(45mm)
See
Detail A
1.6"
(41mm)
23.9"
(608mm)