Vertiv™ XTE 802G Generator Room Walk-In-Cabinet Description and Installation Manual
36
DANGER!
RISK OF ELECTRICAL SHOCK, GENERAL
Do not install equipment showing any physical damage. If packaging is damaged, do not accept receipt from the shipper.
CAUTION!
PREVENT EQUIPMENT DAMAGE, PROPER HANDLING
Do not stack nor lay the XTE 802G on its side.
WARNING!
RISK OF INJURY, FROM UNSECURED XTE 802G
Do not pull cables or terminate cables until XTE 802G has been properly secured in its mounted position.
CAUTION!
PREVENT EQUIPMENT DAMAGE, FROM CONDENSATION
Until the XTE 802G is secured and sealed, weather protection shall be maintained to prevent moisture and condensation
from entering ports or openings into the conditioned space within.
General
For short-term storage, the XTE 802G should not be exposed to temperatures that exceed the temperature range of –40 °C (–40 °F)
to +70 °C (+158 °F).
For long-term storage, the XTE 802G and packaging should be kept dry and not be exposed to temperatures outside the range of –10
°C (+14 °F) to +40 °C (+104 °F).
Once packaging has been discarded and the XTE 802G has been securely placed in its mounted position, the XTE 802G may be
exposed to conditions from –40 °C (–40 °F) to +46 °C (+115 °F).
6.6
Unpacking and Preparing the XTE 802G at the Installation Site
Safety Precautions
DANGER!
Do not install any additional equipment until the XTE 802G is secured in its mounted position.
CAUTION!
TO AVOID EQUIPMENT DAMAGE:
DO NOT REMOVE the exterior packaging or wrap from the XTE 802G until the XTE 802G is transported to the installation
site. Control moisture and condensation inside the XTE 802G until it is turned up for service.
General
•
The XTE 802G is shipped from the manufacturer with plastic wrap to protect the XTE 802G during shipment.
•
If the external packaging appears excessively damaged, do not accept the unit from the shipper as interior damage may not
be apparent.
•
CAREFULLY remove all packaging material from around the XTE 802G. Dispose of the packaging according to local
practices.
•
On receipt at the site, inspect the XTE 802G to make sure there is no damage to equipment. Check the packing slip to make
sure all components are received. If any components are damaged or not received, contact your supervisor for further
instructions.
•
Close and latch all doors in preparation for XTE 802G placement.
WARNING!
Do not open any doors on the XTE 802G unless it is secured in its mounted position, or securely restrained
against unexpected movement or tipping.