NUMBER OF
BATTERIES/CABINETS
LOAD PERCENT OF
CAPACITY
230VAC RT MODELS
5KVA
6KVA
10KVA
Internal Battery
+ 1 External
Battery Cabinet
10%
273
249
209
20%
143
116
105
30%
107
86
63
40%
80
61
44
50%
64
45
34
60%
49
36
26
70%
38
29
21
80%
33
24
17
90%
29
21
14
100%
24
18
12
Internal Battery
+ 2 External
Battery Cabinets
10%
476
431
327
20%
254
207
164
30%
191
158
103
40%
146
113
76
50%
119
89
56
60%
94
69
44
70%
72
56
37
80%
63
47
29
90%
56
42
24
100%
47
37
22
Internal Battery
+ 3 External
Battery Cabinets
10%
689
627
450
20%
374
299
221
30%
274
226
141
40%
211
165
105
50%
173
130
82
60%
137
105
65
70%
111
88
53
80%
97
73
43
90%
88
64
37
100%
74
58
33
Table 9.4 Battery run times, minutes (continued)
Vertiv
| Liebert GXT4 Installer/User Guide |
60
Summary of Contents for GXT4-10000RT230
Page 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA Installer User Guide...
Page 6: ...Vertiv Liebert GXT4 Installer User Guide 6...
Page 10: ...Vertiv Liebert GXT4 Installer User Guide 10 This page intentionally left blank...
Page 20: ...Vertiv Liebert GXT4 Installer User Guide 20 This page intentionally left blank...
Page 30: ...Vertiv Liebert GXT4 Installer User Guide 30 This page intentionally left blank...
Page 40: ...Vertiv Liebert GXT4 Installer User Guide 40 This page intentionally left blank...
Page 48: ...Vertiv Liebert GXT4 Installer User Guide 48 This page intentionally left blank...
Page 56: ...Vertiv Liebert GXT4 Installer User Guide 56 This page intentionally left blank...
Page 64: ...Vertiv Liebert GXT4 Installer User Guide 64 This page intentionally left blank...
Page 65: ......