9.1 Auto-Learning Battery Run Times
As batteries age, the estimated run times may become less accurate. The Liebert GXT4 is programmed to
“learn” from a full battery discharge and modify the estimated run time for the measured battery capacity.
This can improve accuracy and compensate for aging batteries or batteries that operate at different
ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
•
The UPS must have a steady load that is greater than 20%.
•
The UPS must be at 100% charge at the start of a battery discharge.
•
The battery discharge must continue uninterrupted until the batteries reach their end-of-
discharge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the
battery above table will be restored. This will override any value that is auto-learned.
Vertiv
| Liebert GXT4 Installer/User Guide |
62
Summary of Contents for GXT4-10000RT230
Page 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA Installer User Guide...
Page 6: ...Vertiv Liebert GXT4 Installer User Guide 6...
Page 10: ...Vertiv Liebert GXT4 Installer User Guide 10 This page intentionally left blank...
Page 20: ...Vertiv Liebert GXT4 Installer User Guide 20 This page intentionally left blank...
Page 30: ...Vertiv Liebert GXT4 Installer User Guide 30 This page intentionally left blank...
Page 40: ...Vertiv Liebert GXT4 Installer User Guide 40 This page intentionally left blank...
Page 48: ...Vertiv Liebert GXT4 Installer User Guide 48 This page intentionally left blank...
Page 56: ...Vertiv Liebert GXT4 Installer User Guide 56 This page intentionally left blank...
Page 64: ...Vertiv Liebert GXT4 Installer User Guide 64 This page intentionally left blank...
Page 65: ......