Chapter 1 Overview 9
APM 300 Integrated UPS Single Module And Parallel System User Manual
Common battery mode
Common battery function means that in UPS paralleling, the UPS modules can share a battery string to save
cost and space and improve efficiency.
Note
Batteries of different manufacturers, models or used time cannot be used together.
Frequency converter mode
The UPS can be programmed into frequency converter mode for either 50Hz or 60Hz stable output frequency.
The input frequency may vary from 40Hz to 70Hz. In this mode, it is required to open the maintenance bypass
switch to disable the static bypass operation, and the battery becomes optional depending on any
requirement to operate in battery mode.
Dual bus (LBS) system mode
A dual bus system consists of two independent UPS single unit systems. The dual bus system has high
reliability and is suitable for load with multiple inputs. For single input load, an optional STS can be installed to
power the load. For the operation principle diagram of the dual bus system mode, see Figure 7-5.
1.6
Battery Management (Set By Commissioning Engineer)
1.6.1
Normal Function
1. Constant current boost charge.
The charge current can be set.
2. Constant voltage boost charge.
The boost charge voltage can be set as required by the type of battery.
For VRLA batteries, the maximum boost charge voltage should not exceed 2.4V/cell.
3. Float charge.
The float charge voltage can be set as required by the type of battery.
For VRLA batteries, the float charge voltage should be between 2.2V/cell and 2.3V/cell.
4. Float charge temperature compensation (optional).
The temperature compensation coefficient can be set as required by the type of battery.
5. EOD protection.
When the battery voltage drops to the EOD voltage, the battery converter shuts down automatically and the
battery is isolated to avoid further battery discharge. The EOD voltage is settable from 1.6V/cell to 1.75V/cell
(VRLA) or 0.9V/cell to 1.1V/cell (NiCd).
6. Battery low pre-warning time.
The battery low pre-warning time is adjustable between 3min and 60min. The default setting is 5min.
1.6.2
Advanced Function
The UPS provides battery maintenance test function. Battery maintenance test is also called as battery
self-test. At periodic intervals, 20% of the rated capacity of the battery will be discharged automatically, and
the actual load must exceed 20% of the UPS nominal capacity. If the load is less than 20%, the automatic
discharge cannot be executed. The periodic interval can be set from 30 to 360 days. The battery self-test can
be disabled.
Conditions: battery at float charge for at least 5h, load equal to 20%
~
80% of rated UPS capacity.