Chapter 3 Electrical Installation 23
APM 300 Integrated UPS Single Module And Parallel System User Manual
3.2.2
Input Dry Contact Port
The input dry contact ports J7 and J8 provide battery room environment, battery ground fault and battery
temperature signals. The ports are shown in Figure 3-4 and described in Table 3-3.
12V
J7
+12V
BtG
EN
V
GN
D
BAT
-O
UT
+12V
J8
Figure 3-4
Input dry contact ports J7 and J8
Table 3-3
Description of input dry contact ports J7 and J8
Position
Name
Description
J7.1
ENV/GEN
Battery room environment detection (normally
closed)/Generator connected
J7.2
BtG
Battery ground fault
J7.4
+12V
+12V power
J8.2
+12V
+12V power
J8.3
BAT_OUT
Battery temperature detection
J8.4
GND
Power ground
1. The default function of J7.1 is 'battery room environment detection', then 'generator connected' must be configured by
configuration software before becoming active. When the function of J7.1 becomes active, the charger current can be
limited through software to a percentage of the full charger current (0
~
100%).
2. Activating the preceding dry contacts turns the battery charger off.
3.2.3
BCB Port
J6 is the BCB port. The port is shown in Figure 3-5 and described in Table 3-4.
12V
J6
OL
12V 12V
GN
D
FB
DR
V
Figure 3-5
BCB port
Table 3-4
BCB port description
Position
Name
Description
J6.1
DRV
BCB driver signal (reserved)
J6.2
FB
BCB contact state (reserved)
J6.3
GND
Power ground
J6.4
OL
BCB online input (normally open). This pin will become active when the BCB port is connected
The connection between the BCB port and the BCB is shown in Figure 3-6.