64 Chapter 8 Options
APM 300 Integrated UPS Single Module And Parallel System User Manual
1. Remove the cover of Intellislot port. Note to reserve the removed screws and take care of the cover for
future use.
2. Insert the SIC card (along two sides of the Intellislot port) into the port position recommended in Table 8-1,
and then fasten the screws.
For more information of the SIC card, refer to
Site Interface Web/SNMP Agent Card User Manual
in accessory.
8.2.5
Relay Card
The UPS provides relay card for the user to use dry contact signals to monitor the UPS. It is hot pluggable for
easy installation.
The relay card can provide four channels of relay digital signal output to the remote site. They are UPS on
Battery, Battery Low, UPS on Bypass or in Standby, UPS Faulty. Each dry contact signal output channel provides
both normally open and normally closed ports. The relay card can also receive three channels of digital signal
input, two of which control the UPS turn-on and turn-off respectively, the third is reserved.
Appearance and hardware description
The appearance of the relay card is shown in Figure 8-4.
DIP switch
DB25 connector
DIP switch
DB25 connector
Figure 8-4
Relay card appearance
The DIP switch is used to configure the UPS turn-on and turn-off signal input function of the relay card. The
DB25 connector provides dry contact signal input and output. The pins of the DB25 connector are described
in Table 8-2.
Table 8-2
DB25 connector pin description
Pin No.
Pin name
Description
Pin 1
Va, power output
9
~
15Vdc (reserved for factory use)
Pin 14
K0_NO, Channel 0 dry contact normally open output contact
Closed: UPS on Battery
Electrical
parameter:
30Vdc/1.8A,
resistive load
Pin 2
K0_COM, Channel 0 dry contact common output contact
Pin 15
K0_NC, Channel 0 dry contact normally closed output contact Open: UPS on battery
Pin 3
K1_NO, Channel 1 dry contact normally open output contact
Closed: Battery Low
Pin 16
K1_COM, Channel 1 dry contact common output contact
Pin 4
K1_NC, Channel 1 dry contact normally closed output contact Open: Battery Low
Pin 17
K2_NO, Channel 2 dry contact normally open output contact
Closed: UPS on Bypass or
in Standby
Pin 5
K2_COM, Channel 2 dry contact common output contact
Pin 18
K2_NC, Channel 2 dry contact normally closed output contact
Open: UPS on Bypass or in
Standby
Pin 6
K3_NO, Channel 3 dry contact normally open output contact
Closed: UPS Faulty
Pin 19
K3_COM, Channel 3 dry contact common output contact
Pin 7
K3_NC, Channel 3 dry contact normally closed output contact Open: UPS Faulty
Pin 24
DRY_IN2, Channel 2 dry contact signal input
Reserved
Pin 12
DRY_IN1, Channel 1 dry contact signal input
The UPS is turned off if this contact is
closed for more than one second
Pin 25
DRY_IN0, Channel 0 dry contact signal input
The UPS is turned on if this contact is
closed for more than one second