39
User Manual 10H52258UM60 - Rev. 3 - 01/2019
Operation Control and Display
APM 400/600
5.8.1
System Information Window
This window displays System Info, such as current time, name of the UPS, Configuration, and Alarm Silencing
state. This window does not require any interaction on the part of the operator.
Table 5.6 lists the information that appears on the screen.
Table 5.6
Item
Explanation
APM
Name of the UPS series
Single
Single: UPS module system with dual conversion
APM 400 kVA
UPS power is 400kVA
APM 600 kVA
UPS power is 600kVA
16:21:17
Current time (format: 24 hours, hour: minute: second)
/
Audible alarm enabled or disabled
: disabled
: enabled
New alarm being shown
5.8.2
Menu Window and Data Window
The Menu window displays the Data window menu. The data window displays the menu items and data
associated with the menu selected in the Menu window. The Menu window and Data window helps users when
browsing through the UPS parameters and setting up the UPS functions.
Table 5.7 below lists the menu items, complete with a short description.
Table 5.7
Menu
Item
Description
Mains
L-N voltage (V)
Phase voltage
L-N current (A)
Phase current
Frequency (Hz)
Input frequency
L-L voltage (V)
Line voltage
Power factor
Power factor
Bypass
L-N voltage (V)
Phase voltage
Frequency (Hz)
Bypass frequency
L-L voltage (V)
Line voltage
Output
L-N voltage (V)
Phase voltage
L-N current (A)
Phase current
Frequency (Hz)
Output frequency
L-L voltage (V)
Line voltage
Power factor
Power factor
Load
Sout (kVA)
Sout: apparent power
Pout (kW)
Pout: active power
Qout (kVAR)
Qout: reactive power
Load level (%)
Load (expressed in percentage of the UPS rating load )
Crest factor
Output current crest factor
System
Sout (kVA)
Sout: apparent power
Pout (kW)
Pout: active power
Qout (kVAR)
Qout: reactive power
Single unit, no parallel system
data
Displayed in this data window when the UPS is
configured as a single unit
Battery
Battery voltage (V)
Battery bus voltage