User Manual 10H52258UM60 - Rev. 3 - 01/2019
40
APM 400/600
Operation Control and Display
Menu
Item
Description
Battery current (A)
Battery bus current
Battery temperature (°C)
Battery temperature
Battery remain time (Min.)
Remaining battery backup time
Battery capacity (%)
Percentage of battery life as compared to a new battery
Battery boost charging
Battery is boost charging
Battery float charging
Battery is float charging
Battery is not connected
Battery is not connected
Event
(active alarm)
Displays the active alarms
Event
(active alarm)
Displays the active alarms
Records
(alarm history)
Displays the alarm history
Language
(language option)
There are 13 available display languages
Settings
Display contrast
Adjusts the LCD contrast
Date format set
Three different formats may be selected: MM/DD/YYYY,
DD/MM/YYYY, YYYY/MM/DD
Date & time
Sets the date and time
Comm1 baud rate
Sets the Intellislot port 1 communication baud rate
Comm2 baud rate
Sets the Intellislot port 2 communication baud rate
Comm3 baud rate
Sets the Intellislot port 3 communication baud rate
Communication address
Applicable to RS485 communication
Single Group Batt Cap
Sets the capacity of battery unit
Battery Cells Number
Sets the number of battery cells connected to the UPS
Equalize Charge Allowed
Indicates whether the battery boost charge is enabled or
not
Temp Compensation
Enabled, Disabled
Shared Battery
Enabled, Disabled
System Configuration
Single, Parallel
Parallel Requisite units
Basic number of single modules in parallel system
Parallel Redundant units
Redundant number of single modules in parallel system
Parallel ID
Provides only one ID code for the individual modules in a
parallel system, when 'Parallel' is set
ECO Mode
Normal, ECO
Output Frequency Level
Sets the system output frequency (unit: Hz); 50/60