User Manual 10H52258UM60 - Rev. 3 - 01/2019
88
APM 400/600
Specifications
11
Specifications
This covers the APM unit Technical, Mechanical and Electrical Specifications, as well as the Environmental
Operating Specifications.
11.1
Conformance and Standards
The UPS has been designed to comply with the European and international standards listed in Table 12-1.
Table 12.1 European and international standards
Item
Normative reference
General safety requirements for UPS
IEC/EN62040-1+A1:2013/AS62040-1
EMC requirements for UPS
IEC/EN62040-2:2006/AS62040-2 (Class C3)
Method of specifying the performance and test requirements
of UPS
IEC/EN62040-3/AS62040-3 (VFI SS 111)
The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards
for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and
construction (IEC/EN/AS60146 series and 60529).
11.2
Environmental Specifications
Item
Unit
Rated power (kVA)
400-600
Noise within 1m (in the front)
dB (A)
70
Altitude
m
≤ 1500; derate power by 1% per 100m between 1500m and
3000m
Relative humidity
%RH
0 ~ 95%, non condensing
Operating temperature
°C
0 ~ 40°C
Storage and shipping temperature for
UPS
°C
Storage: -25°C ~ +55°C; shipping: -40°C ~ +70°C
Over-voltage level
Level 2
Pollution level
Level 2
Earthing network systems
TN, TT, IT
11.3
Mechanical Specifications
Item
Unit
Rated power (kVA)
400
600
Dimensions (D × W × H)
W/out packing
mm
1000 x 1400 x 2000
1000 × 1800 × 2000
With packing
mm
1135 x 1530 x 2260
1135 × 1930 × 2260
Net weight
kg
928
1244
Gross weight
Kg
1028
1344
Color
RAL
7021
Protection rating, IEC (60529)
IP20