Component
Quantity
Unit Model
Water leakage detection sensor bracket
1
CRC30, CRC60
Cable for water leakage detection sensor
1
CRC30, CRC60
Plastic plug head
4
CRC30, CRC60
M12 × 30 hexagon bolt
8
CRC30, CRC60
Brass connector for drainage
1
CRC30, CRC60
Brass connector for humidifier
1
CRC30
Drainage hose
1
CRC30, CRC60
Electrical schematic diagram
1
CRC30, CRC60
Hose clamp
1
CRC30, CRC60
Baying bracket
8
CRC30, CRC60
Ramp
2
CRC30, CRC60
User manual
1
CRC30, CRC60
2.5 System Data
Parameter
CRC30
CRC60
Width mm (in.)
300 (11.8)
300 (11.8)
Input power
400 V, 3-phase, 50 Hz
230 V, 1-phase, 50 Hz
Total airflow m
3
/h (CFM)
Rated value: 5100 (3001.7)
Maximum value: 5900 (3473)
Rated value: 7700 (4532)
Maximum value: 7700 (4532)
Input power consumption without heater and
humidifier kW
Rated value: 1.06
Maximum value: 1.68
Rated value: 1.9
Maximum value: 1.9
Number of fans
7
8
Heating capacity kW
3
-
Humidification capacity kg/h (lb/h)
2 (4.4)
-
Condensate pump capacity L/min @ 5 m
3.5
3.5
Air filtration efficiency
G4
G4
Table 2.3 Technical Specifications
Parameter
CRC30
CRC60
Return-air condition
35 °C (95 °F) DB, 24% RH, 10 °C (50 °F) EWT, 5.5
°C (10 °F) Water Rise
38 °C (100 °F) DB, 24% RH, 15 °C (59 °F) EWT, 5.5
°C (10 °F) Water Rise
Net total capacity kW
Rated value: 27.3
Maximum value: 30.2
Rated value: 39.5
Maximum value: 39.5
Net sensible capacity kW
Rated value: 27.3
Rated value: 39.5
Table 2.4 Performance Data
2 Product Overview
10
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual