8.
Loosen the hose clamp and disconnect the water supply pipe under the humidifier.
9. Loosen the rubber belt around the cylinder and pull the cylinder out of the support bracket.
10. Replace the cylinder.
Figure 9.5 Removing Humidifier (Only for CRC30)
Item
Description
Item
Description
1
Rear door
5
Water drainage connection
2
Steam pipe connection
6
Water inlet pipe connection
3
Electrode wire connection
7
Support bracket for humidifier
4
Level sensor connection
9.10 Dismantling the unit
CAUTION: To prevent possible harm to the environment or human health from uncontrolled waste disposal,
recycle it responsibly to promote the sustainable reuse of material resources. To return your used device,
please use the return and collection systems or contact the retailer where the product was purchased. They
can take this product for environmental safe recycling.
NOTICE
9 Maintenance
64
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual