4 Installing in Enclosure Row
4.1 Leveling the Unit
To level the unit:
1.
Use an adjustable wrench to loosen the fixing nut on each foot in counterclockwise direction.
2.
Rotate the hex bolt on the base of each foot in clockwise or counterclockwise direction until the foot rises or
falls to a suitable position. Use a level to ensure that the cabinet is level.
3.
Tighten the fixing nut on each foot.
Figure 4.1 Leveling the Unit
Item
Description
1
Fixing nut
2
Hex bolt
4.2 Removing the Feet and Fixing the Unit (Optional)
NOTE: If the machine room has a mounting bracket, and its width does not exceed 30 mm (1.2 in.), you can remove the
feet and fix the unit onto the mounting bracket.
To remove the feet and fix the unit:
1.
Use an adjustable wrench to loosen the fixing nut on each foot in counterclockwise direction. Rotate the hex
bolt counterclockwise until each foot drops from the unit.
2.
The unit provides four holes (diameter: 13.5 mm (0.5 in.)) on the bottom frames of the unit. Install M12 x 25
screws in the holes to fix the unit onto the floor bracket of the equipment room.
4 Installing in Enclosure Row
19
Vertiv™ Liebert® CRV CRD25 and CRD35 Row-Based Cooling System User Manual