Item
Description
1
Main grounding point
4.5 Removing Compressor Fixing Plates
The fixing plates are used to prevent the compressor from vibrating during transportation. Once the unit has been installed
on site, you need to remove these fixing plates. To remove fixing plates:
1.
Open the rear door.
2.
Remove filters.
a. Pull the handle in the middle of the fastening plate above the upper filter to remove the plate. Then
remove the upper filter.
b. Tilt the fastening plate above the lower filter and remove the plate. Then remove the lower filter.
Figure 4.5 Removing the Upper and Lower Filters
Item
Description
Item
Description
1
The handle in the middle of the fastening plate
3
The fastening plate above the lower filter
2
The fastening plate above the upper filter
3.
For Vertiv™ Liebert® CRV CRD25 cooling unit, remove two fixing plates from the compressor. To remove each
fixing plate, loosen the M8 x 60 screw on it so as to remove the plate. Then torque the screw at 12±1 Nm
(8.85±0.74 ft/lb).
4 Installing in Enclosure Row
22