Symptom
Possible
Causes
Check or Remedy
ActuatorMotors
No24VAC
powerto
motor
Check for24VACbetweenP22-3 andP22-5(open), orP22-1 andP22-5(closed).
Chilledwaterorhot
water/steamvalve
not opening
Motor
operatesbut
valve won’t
open
Check linkage foradjustmentandbe sure that it istight onthe valve.
ModulatingMotors
No24VAC
powerto
motor
Check control fusesandpowerat PCB andPCT.
Nosignal
fromcontrol
Check DCvoltage onprintedcircuit boardinmotor. Terminal No. 1 isgroundedandNo. 3 ispositive. DCvoltage
shouldvary from0.8to2.0 VDCorabove astemperature control isvariedbelowroomtemperature oncooling
valve orabove roomtemperature onheatingvalve.
Motornot
working
Remove wiresonterminal No. 1 andNo. 3 fromthe motor(donot short). With24VACpowerfromTRtoTRjumper
terminal 1 and2 onmotortodrive open. Remove jumpertodrive closed, if motorfailstowork, replace it.
Table 10.2 Chilled water troubleshooting
Symptom
Possible Cause
Check or Remedy
No
humidification
Humidifierpannot filling
Check watersupply.
Check fill valve operation
Check drainstandpipe adjustment
Check forcloggedwaterline
Check float orientation(see )
Control not callingfor
humidity
Check monitorstatus
Humidity contact not
pullingin
Check visually. If contact ismade, check line voltage aftercontactorandfusesorCBs.
Check foropenhumidifiersafety stat. JumperbetweenterminalsP35-6andP35-5. If contactorpullsin,
replace safety. Remove jumper.
Humidifierbulbburned
out
Replace bulb. Loosenleadonoldbulb. Trimexcessleadlengthonnewbulbtoavoidshorts.
Table 10.3 Humidifier—infrared troubleshooting
Vertiv | Liebert® CW™Installer/User Guide
78
Summary of Contents for Liebert CW 038
Page 14: ...Vertiv Liebert CW Installer User Guide 14 Thispageintentionally left blank...
Page 22: ...Vertiv Liebert CW Installer User Guide 22 Thispageintentionally left blank...
Page 38: ...Vertiv Liebert CW Installer User Guide 38 Thispageintentionally left blank...
Page 80: ...Vertiv Liebert CW Installer User Guide 80 Thispageintentionally left blank...
Page 102: ...Vertiv Liebert CW Installer User Guide 102 Thispageintentionally left blank...
Page 108: ...Vertiv Liebert CW Installer User Guide 108 Thispageintentionally left blank...