4.2 Unit Storage
Store the drycooler in the original packaging in an area protected from excessive dirt, debris and contact damage until final
installation
4.3 Handling Unit on the Skid
Transport unit using a fork lift or a crane with sling and spreader bars.
Using a forklift
NOTICE
Risk of improper forklift handling. Can cause unit damage.
Keep the forklift tines level and at a height that will fit under the skid.
•
Make sure the forks (if adjustable) are spread to the widest allowable distance to still fit under the skid.
•
Type of forklift used will depend on the terrain the unit is to be moved across during handling.
•
Minimum forklift fork length:
•
for 1 fan and two fan units—48 in (1219 mm)
•
for 3 fan and 4 fan units—72 in. (1829 mm)
•
for 6 fan units—72 in. (1829 mm)
•
for 8 fan units—96 in. (2438 mm)
•
When moving the packaged unit, do not lift it any higher than 6 in. (152 mm). If the unit must be lifted higher
than 6-in. (152 mm), you must exercise great care, and no one may be closer than 20 ft (6 m) to the lift point.
•
We recommend lifting one end off the ground no more than 6 in. (152 mm)and using the forklift to push or pull
the unit.
Figure 4.1 Forklift position with 1 to 8fan units
Using a Crane
•
We recommend using slings rated for the unit weight.
•
Spreader bars must be used for sling stability and to keep the slings from pressing against the unit. Make sure
spreader bars are wider than the unit.
•
Place the slings near the ends of the unit, under the top deck boards of the skid.
Vertiv | Liebert® Drycooler Installer/User Guide
18
Summary of Contents for Liebert Drycooler
Page 1: ...Liebert Air cooled Direct drive Drycooler Installer User Guide 50 Hz and 60 Hz ...
Page 10: ...Vertiv Liebert Drycooler Installer User Guide 6 This page intentionally left blank ...
Page 20: ...Vertiv Liebert Drycooler Installer User Guide 16 This page intentionally left blank ...
Page 24: ...Figure 4 2 Removing Protective Material Vertiv Liebert Drycooler Installer User Guide 20 ...
Page 34: ...Vertiv Liebert Drycooler Installer User Guide 30 This page intentionally left blank ...
Page 54: ...Vertiv Liebert Drycooler Installer User Guide 50 This page intentionally left blank ...
Page 62: ...Vertiv Liebert Drycooler Installer User Guide 58 This page intentionally left blank ...
Page 66: ...Vertiv Liebert Drycooler Installer User Guide 62 This page intentionally left blank ...
Page 68: ...Vertiv Liebert Drycooler Installer User Guide 64 This page intentionally left blank ...
Page 101: ...Vertiv Liebert Drycooler Installer User Guide ...