Liebert EXL S1
Technical data
User Manual 10H52226UM60 - Rev. 1 - 01/2017
1
02
9. TECHNICAL DATA
9.1. Liebert EXL S1
3
00-500kVA
General conditions of technical data table:
The data shown are typical and refer to 25°C ambient temperature and nominal input and output
conditions, unless otherwise specified. Not all data shown apply simultaneously. Data apply to the
standard version, unless otherwise specified.
For test conditions and measurement tolerances not specified in the table, see the Witness Test
Report procedure.
UPS model
Liebert EXL S1
Power (kVA)
300
400
500
System data
AC/AC efficiency in VFI
mode without charging
current, with resistive load
1)
2)
25% load (%)
50% load (%)
75% load (%)
100% load (%)
up to
96.4
up to
96.8
up to
96.7
up to
96.3
AC/AC efficiency in Intelligent ECO mode without
charging current, at maximum resistive load
1)
2)
98.7
Heat dissipation at nominal
output load
Float mode VFI (kW)
(Btu/h)
10.4
13.8
17.3
35400
47200
59000
ECO (kW)
(Btu/h)
3.6
4.7
5.9
12140
16180
20230
Noise at 1 m as per ISO 3746
1)
2)
(dBA ± 2dBA)
≤
65 @ partial load
Noise at 1 m as per ISO 3746
1)
2)
(dBA ± 2dBA)
≤
69
≤
71
≤
73
Protection degree with doors open
IP20
Mechanical dimensions:
Height (mm)
1950
Width (mm)
1000
1250
Depth (mm)
900
Shipping Weight (kg)
775
1060
Net Weight (kg)
725
990
Number of cabinets
1
Frame color
RAL7021
Floor area (depth w/o handle: 830 mm) (m
2
)
0.90
1.13
Floor loading (kg/m
2
)
806
880
Cable entry
Bottom
Service access
Front and top
Cooling
(m
3
/h)
Forced Ventilation, front air intake, top air outlet
2522
3153
Location
Indoor (free from corrosive gases and conductive dust)
Operating temperature (°C)
0-40
Max. relative humidity @ 20°C (non condensing)
(%)
up to 95
Summary of Contents for Liebert EXL
Page 1: ...Liebert EXL User Manual...
Page 2: ...Liebert EXL UNINTERRUPTIBLE POWER SUPPLY USER MANUAL 10H52226UM60 rev 1...
Page 7: ...Liebert EXL S1 6 User Manual 10H52226UM60 Rev 1 01 2017...
Page 36: ...Preparation For Use Liebert EXL S1 35 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 74: ...CONNECTIVITY PANELS Liebert EXL S1 73 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 84: ...Normal and safe operation Liebert EXL S1 83 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 86: ...Maintenance Liebert EXL S1 85 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 94: ...PARALLEL CONFIGURATION Liebert EXL S1 93 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 102: ...Options Liebert EXL S1 101 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...