Liebert EXL S1
Technical data
User Manual 10H52226UM60 - Rev. 1 - 01/2017
1
08
Short circuit current for ≤200ms
2,2In
Nominal output voltage (V)
380/400/415
Nominal output frequency (Hz)
50 (60 selectable)
Voltage stability in steady state condition for input variations (AC &
DC) and step load (0 to a nominal load) (%)
±1
Voltage stability in dynamic condition for i/p variations (AC & DC) and
step load
Complies with IEC/EN 62040 - 3 CLASS 1
Voltage stability in steady state with nominal load imbalance (0, 0, 100)
(%)
±3
Output frequency stability
synchronized with Bypass line
(%)
±2 default (2, 3, 4, 5 selectable)
synchronized with internal
clock (%)
±0.1
Frequency slew rate (Hz/s)
<1 default (selectable up to 5Hz)
Output voltage distortion at nominal linear load (%)
≤1
.
5
Output voltage distortion at @ reference non-linear load as per IEC/
EN62040-3 (%)
<5
Load Crest Factor without derating (I
pk
:I
rms
)
3:1
Phase angle accuracy with balanced loads
±1°
Phase angle accuracy with 100% unbalanced loads
±3°
Static Bypass
Nominal Bypass voltage
6)
(V)
400 (3ph + N + PE) or 400 (3ph + PE)
Voltage range (%)
±10 (5 to 15 selectable)
Nominal frequency (Hz)
50 (60 selectable)
Frequency range (%)
±1 (2, 3, 4 selectable)
Overload capacity
125%
10 min.
150%
1 min.
700%
600 ms
1000%
100 ms
SCR
I
2
t @ T
vj
=125 °C 10 ms (kA
2
s)
2530
5611
I
TSM
@ T
vj
=125 °C 10 ms (A)
22500
33500
Bypass fuses
10)
1250A, aR class
I
2
t 860kA
2
s (@400V)
prearc 355kA
2
s
2000A, aR class
I
2
t 3100kA
2
s (@400V)
prearc 1150kA
2
s
Prospective short circuit current Icp
10)
11)
(kA)
100
Transfer time with inverter
synchronous to Bypass
Inverter to Bypass (ms)
No Break
Bypass to Inverter (ms)
≤2
Default transfer delay time (inverter to Bypass) with inverter not
synchronized to Bypass (ms)
20
1)
For tolerances see IEC/EN 60146-1 or DIN VDE 0558. The data refers to 25°C ambient temperature
2)
Nominal input voltage and input frequency
UPS model
Liebert EXL S1
Power (kVA)
600
800
1000
1200
Summary of Contents for Liebert EXL
Page 1: ...Liebert EXL User Manual...
Page 2: ...Liebert EXL UNINTERRUPTIBLE POWER SUPPLY USER MANUAL 10H52226UM60 rev 1...
Page 7: ...Liebert EXL S1 6 User Manual 10H52226UM60 Rev 1 01 2017...
Page 36: ...Preparation For Use Liebert EXL S1 35 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 74: ...CONNECTIVITY PANELS Liebert EXL S1 73 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 84: ...Normal and safe operation Liebert EXL S1 83 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 86: ...Maintenance Liebert EXL S1 85 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 94: ...PARALLEL CONFIGURATION Liebert EXL S1 93 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 102: ...Options Liebert EXL S1 101 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...