CONNECTIVITY PANELS
Liebert EXL S1
69
User Manual 10H52226UM60 - Rev. 1 - 01/2017
4.2.1. XS3 - Slot for Connectivity Products
This slot is the recommended interface for the SNMP Adapter ManageUPS NET. This Adapter
provides an independent external network interface for communication with connectivity products.
The Slot is SELV - isolated from UPS primary circuits.
4.2.2. XS6 - Slot for LIFE
TM
Products
This slot is the reserved interface for LIFE
TM
modem card. This card provides an independent external
modem interface for communication with LIFE
TM
service station. Ask your local Vertiv dealer for more
details on LIFE
TM
and its benefits for your UPS system.
When a LIFE
TM
modem card is inserted into XS6, interface XP6 is connected to Slot XS6 to allow
parameterisation and diagnosis of the LIFE
TM
modem card. The Slot is SELV - isolated from UPS
primary circuits.
4.2.3. XP6 -
Serial Interface for Connectivity Products (serial input/output)
The service Interface is a SUB-D 9pin male connector for RS232 serial communication. It is used for
communications with external LIFE
TM
modem (e.g. GSM modem) or other special Vertiv applications.
The Interface is SELV - isolated from UPS primary circuits.
4.2.4. XP10 - EPO connector
Connection with customer plant:
7-wire connector with screw terminals and screws for fixing it.
Connection should be as follows:
The emergency stop action shuts down the rectifier, inverter, and static bypass. It does not however
internally disconnect the input mains supply. If required, this additional action can be facilitated by
acting on a second contact of the emergency stop switch placed on an upstream breaker.
To perform a remote emergency power off, it is necessary to connect an emergency stop button to
the UPS via a twisted/shielded cable not exceeding 20 m in length. The contact must be "CLOSED"
under normal operating conditions. When this contact opens, the load will be cut off and a fault will
EPO
Customer plant
IO board
1
2
3
4
5
6
7
Summary of Contents for Liebert EXL
Page 1: ...Liebert EXL User Manual...
Page 2: ...Liebert EXL UNINTERRUPTIBLE POWER SUPPLY USER MANUAL 10H52226UM60 rev 1...
Page 7: ...Liebert EXL S1 6 User Manual 10H52226UM60 Rev 1 01 2017...
Page 36: ...Preparation For Use Liebert EXL S1 35 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 74: ...CONNECTIVITY PANELS Liebert EXL S1 73 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 84: ...Normal and safe operation Liebert EXL S1 83 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 86: ...Maintenance Liebert EXL S1 85 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 94: ...PARALLEL CONFIGURATION Liebert EXL S1 93 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 102: ...Options Liebert EXL S1 101 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...