Vertiv
| Liebert
®
EXM
™
EBC
™
480V User Manual |
31
Cable Entry Area
15.8" x 10.4"
(401mm x 264mm)
Cable Entry Area
12.6" x 12.1"
(320mm x 310mm)
Cable Entry Area
9.3" x 14.2"
(236mm x 361mm)
Alber Service
Plates
19.3" x 14"
(490mm x 356mm)
Alber BDSUI
(Optional)
34.3"
(871mm)
39.8" (1011mm)
Door Closed
47.2" (1200mm)
47.5" (1208mm)
78.8"
(200mm)
6.9" (175mm)
Outside Frame
6.2"
(157mm)
16.8" (419mm)
Outside Frame
FRONT
BOTTOM
Viewed from Floor
TOP
Battery
Breaker
Battery
and Tray
Center of
Gravity
1. 24" (610mm) minimum clearance above unit for air exhaust.
36" (914mm) frtont access required for service.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size and replace.
4. Control wiring and power wiring must be run in separate conduits.
5. Copper cables only are recommended.
6. All wiring must be in accordance with national and local electrical codes.
FRONT
(Without Covers)
RIGHT SIDE
Leveling
Feet
EXM42004
Pg. 1, Rev. 0
12.7" (326mm)
Bracket
Centers
12.7"
(326mm)
Bracket
Centers
Z
X
LEFT SIDE
Panel Removed
FRONT
Door Removed
RIGHT SIDE
Panel Removed
Battery
Breaker
Battery
EXM42004
Pg. 2, Rev. 0
Alber
BDSUi
(Optional)
DC Connection
Busbars
Ground
Bus
Description
Center of Gravity
X
Y
Z
Frame -
No Batteries
495
504
1175
12HX330
495
504
945
12HX400
495
504
930
12HX505
495
504
915
12HX540
495
504
894
HR3500
495
504
950
HR4000
495
504
935
HR5000
495
504
918
HR5500
495
504
892
UPS12-350MR 495
504
950
UPS12-400MR 495
504
935
UPS12-490MR 495
504
898
UPS12-540MR 495
504
898