4.0 SPECIFICATIONS
Table 9
Physical standards and parameters
Battery Cabinet Parameters
Values
Standard Color
Black (ZP-7021)
Front Door Opening (for serviceability)
180°
Degree of Protection for UPS Enclosure
IP 20 (with and without front door open)
Minimum Clearance, Top
24" (610mm)
Minimum Clearance, Back
0"
Minimum Clearance, Sides
0"
Cable Entrance
Top or Bottom
Standards & Conformities
UL 1778 5th Ed.; CSA 22.2 107.3-14
FCC Part 15, Class A; ISTA Procedure 1H; WEEE;
IBC 2012/CBC 2013
Environmental
Storage Temperature Range, °F (°C)
-13°F to 158°F (-25°C to 70°C)
74°F to 80°F (23-27°C) for optimal battery life
Operating Temperature Range, °F (°C)
32°F to 104°F (0 to 40°C)
74°F to 80°F (23-27°C) for optimal battery life
Relative Humidity
up to 95% Non-Condensing
(Operating and Non-Operating)
Maximum Altitude Above MSL, ft (m)
4920 (1500) (as per IEC 62040/3) -
1% Maximum kW derate / 100m rise between 1500-
3000m
Table 10
Battery cabinet system—UPS and Liebert EXM Battery Cabinet
UPS
Rating
kVA
Battery
Cabinet
Breaker
Maximum
Battery
Current, A
Battery
Cabinet
Size, mm
Copper
Wire
Compression
Lug
Bolt
Size
50-100
300A
290
880, 1200
(2) 3/0
54874BE (2
Hole)
1/2"
150
450A
435
880, 1200
(2)
250kcmil
54874BE (2
Hole)
1/2"
200
600A
581
880, 1200
(3)
250kcmil
54874BE (2
Hole)
1/2"
250 *
600A
581
880, 1200
(3)
250kcmil
54874BE (2
Hole)
1/2"
* 250kVA UPS requires a minimum of two cabinets.