Installation Drawings
Vertiv
| Liebert
®
EXM
™
TXC
™
User Manual |
16
Figure 8
Lineup arrangement, Liebert EXM with Liebert EXM TXC, 10-40kVA
Figure 9
Lineup arrangement, Liebert EXM with Liebert EXM TXC, 60-100kVA
FRONT VIEW
78.7"
(2000mm)
7.9"
(200mm)
23.6"
(600mm)
23.6"
(600mm)
55.1" (1400mm)
Dual XFRMR
Cabinet
MBC
UPS
EXM13005
Rev. 1
Notes
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit for air exhaust
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size and
replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in
separate conduits.
7. All wiring is to be in accordance with national and local
electrical codes.
8. All battery cabinets must be positioned on the left side
of the UPS.
EXM13011
Rev. 1
Notes
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit for air exhaust
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size and
replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in
separate conduits.
7. All wiring is to be in accordance with national and local
electrical codes.
8. All battery cabinets must be positioned on the left side
of the UPS.
FRONT
23.6"
(600mm)
23.6"
(600mm)
78.7"
(2000mm)
11.8"
(300mm)
59" (1500mm)
Dual XFRMR
Cabinet
MBC
UPS