3.0 SPECIFICATIONS
Table 3
Physical standards and parameters
Dual Transformer Cabinet
Parameters
Values
Standard Color
Black (ZP-7021)
Front Door Opening (for
serviceability)
More than 180°
Degree of Protection for UPS
Enclosure
IP 20 (with and without front door open)
Minimum Clearance, Top
24" (610mm)
Minimum Clearance, Back
0" (5" [127mm] when seismic brackets are used)
Minimum Clearance, Sides
0"
Cable Entrance
Top or Bottom
Standards & Conformities
UL 71778 5th Ed.; CSA 22.2 107.3-14
ISTA Procedure 1H; WEEE
Environmental
Storage Temperature Range, °F
(°C)
-13°F to 158°F (-25°C to 70°C)
Operating Temperature Range, °F
(°C)
32°F to 104°F (0 to 40°C)
32°F to 86°F (0-30°C) when seismic brackets are
used
Relative Humidity
Up to 95% Non-Condensing
(Operating and Non-Operating)
Maximum Altitude Above MSL, ft
(m)
4920 (1500) (as per IEC 62040/3) -
1% Maximum kW derate / 100m rise between 1500-
3000m
Table 4
Liebert EXM TXC, 10-100k, mechanical characteristics
Mechanical Characteristics
Values
Dimensions, W x D x H, in (mm)
23.625 x 39.375 x 78.75 (600 x 1000 x 2000)
Color
ZP 7021 (Black)
Protection Degree IEC (60529)
IP20 (finger-proof with front doors open or
closed)
Rated Power, kVA
Weight, lb (kg)
10
827 (376)
15
883 (401)
20
941 (428)
30
1280 (582)
40
1307 (594)
60
1569 (713)
80
1815 (825)
100
2043 (929)