Vertiv™ |
Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual
|
39
5.4.2
Liebert
®
IntelliSlot Relay Card Jumper Setup
The Liebert
®
IntelliSlot Relay Card has five jumpers, P3 through P7, as shown in
. Each jumper connects
two pins.
Figure 26
Jumper location and numbering
By default, all five jumpers have shunts installed. The two pins are shunted together to provide the functions
shown in
, allowing relay commons to be tied together.
The jumpers should be removed if there is any external voltage source that may intentionally or inadvertently be
connected to the relay.
Removing the shunt from any two pins breaks the connection between the relay commons so they are not tied
together.
Table 11
Jumper connections
Jumper
Relay
P6
On Battery
P5
UPS Fault
P4
Low Battery
P3
On Bypass
P7
Summary Alarm
NOTE
Refer to the Liebert
®
IntelliSlot Relay Card manual, SL-23211, for additional details. the document is available at
www.vertiv.com
Jumper
P6
Jumper
P5
Jumper
P4
Jumper
P3
Jumper
P7
Front of
Card