Air filter replacement
8.3.3
Torque Requirements
All electrical connections must be tight.
through
provide the torque values for the connections in the UPS and batteries. Use these values
unless the equipment is labeled otherwise.
Table 27
Busbars—Power wiring
Bolt Shaft Size
Lb-in (Nm)
1/2" (M12)
428 (48)
Table 28
Terminal block with compression lugs—Control wiring
AWG Wire Size
or Range
Lb-in (Nm)
#22 - #14
3.5 to 5.3 (0.4
to 0.6)
FRONT
Door Open
Replaceable
Air Filters
Replaceable
Air Filter
Operator
Control Panel