Vertiv™ |
Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual
|
55
7.0 SPECIFICATIONS AND TECHNICAL DATA
7.1
Conformity and Standards
The Liebert
®
EXM has been designed to conform to the following standards:
The Liebert
®
EXM has UL and c-UL approval.
7.1.1
ENERGY STAR
®
Certification
The Liebert
®
EXM UPS is ENERGY STAR certified satisfying “ENERGY STAR Program Requirements Product
Specification for Uninterruptible Power Supplies (UPS) - Eligibility Criteria, Version 2.0.”
7.2
UPS Environmental
The Liebert
®
EXM is designed to operate under the following environmental conditions without damage or
degradation in electrical operating characteristics:
Safety
UL 1778 4th Edition, CSA 22.2 107.3
Surge
IEC 61000-4-5 Criteria B
Harmonics
IEC 61000-3-4
Electrical Fast Transient
IEC 61000-4-4, Criteria B
ESD
IEC 61000-4-2, Criteria B
FCC
Part 15, Class A
Radiated Immunity
IEC 61000-4-3, Criteria A
Conducted Immunity
IEC 61000-4-6, Criteria A
Low-Frequency Signals
IEC 61000-2-2 Criteria A
Transportation
ISTA Procedure 1H
ISO
9001
Misc
OSHA, ASME, NEMA PE-1
Table 13
Environmental requirements
Item
Requirements
Acoustical Noise, dBA, at 55 in. (1.4m)
59
Operating Altitude
4922 ft. (1500m) 1% maximum kW derate per 328 ft. (100m) rise between
4922 and 9843 ft. (15000m and 3000m)
Relative Humidity
95%
Operating Temperature, °F (°C)
104 (40)
UPS Storage/Transport Temperature, °F (°C)
-4 to 158 (-20 to 70)
Table 14
UPS mechanical characteristics
Rated Power, kVA
20 - 100
Dimensions, W x D x H, in (mm)
23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000)
Weight, lb (kg)
See
for weights
Color
RAL 7021 (Black)
Protection Degree IEC (60529)
IP20
Summary of Contents for Liebert EXM